⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.31%
Aluminum Wire (≤3% Drop)2 AWGDrop: 0.29V (2.4%)
Voltage at Load End11.7 VLoss: 0.28 V (4.2 W)
Power & Breaker (125%)0.18 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2.82 V (23.52%)9.2 V4.66 V (38.8%)42.3 WDrop/Amp High
12 AWG3.31 mm²20 A1.77 V (14.78%)10.2 V2.93 V (24.38%)26.6 WDrop/Amp High
10 AWG5.26 mm²30 A1.12 V (9.3%)10.9 V1.84 V (15.34%)16.7 WDrop/Amp High
8 AWG8.37 mm²50 A0.7 V (5.84%)11.3 V1.16 V (9.64%)10.5 WDrop/Amp High
6 AWG13.3 mm²65 A0.44 V (3.68%)11.6 V0.73 V (6.07%)6.6 W~ ≤5%
4 AWG21.15 mm²85 A0.28 V (2.31%)11.7 V0.46 V (3.82%)4.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.22 V (1.83%)11.8 V0.36 V (3.03%)3.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.17 V (1.46%)11.8 V0.29 V (2.4%)2.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.14 V (1.15%)11.9 V0.23 V (1.9%)2.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.11 V (0.91%)11.9 V0.18 V (1.51%)1.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.09 V (0.73%)11.9 V0.14 V (1.2%)1.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.07 V (0.58%)11.9 V0.11 V (0.95%)1.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.05 V (0.46%)11.9 V0.09 V (0.75%)0.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.05 V (0.39%)12.0 V0.08 V (0.64%)0.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.04 V (0.32%)12.0 V0.06 V (0.53%)0.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.03 V (0.28%)12.0 V0.05 V (0.46%)0.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.03 V (0.24%)12.0 V0.05 V (0.4%)0.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.02 V (0.19%)12.0 V0.04 V (0.32%)0.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.02 V (0.16%)12.0 V0.03 V (0.27%)0.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.02 V (0.13%)12.0 V0.03 V (0.21%)0.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.01 V (0.1%)12.0 V0.02 V (0.16%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 30 feet one-way at 12V (DC), you need 4 AWG copper wire. This produces a voltage drop of 0.28V (2.31%) and delivers 11.7V at the load.

What size aluminum wire is required for 15 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 0.29V (2.4%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.