🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.46V (12.17%)
Voltage at Load End11.7 VLoss: 0.3 V (36.9 W)
Power & Breaker (125%)1.5 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A215.59 V (1796.62%)0.0 V355.63 V (2963.59%)26949.3 WDrop/Amp High
12 AWG3.31 mm²20 A135.48 V (1129.0%)0.0 V223.48 V (1862.31%)16934.9 WDrop/Amp High
10 AWG5.26 mm²30 A85.25 V (710.45%)0.0 V140.63 V (1171.91%)10656.8 WDrop/Amp High
8 AWG8.37 mm²50 A53.58 V (446.47%)0.0 V88.38 V (736.47%)6697.1 WDrop/Amp High
6 AWG13.3 mm²65 A33.72 V (280.98%)0.0 V55.62 V (463.48%)4214.6 WDrop/Amp High
4 AWG21.15 mm²85 A21.2 V (176.69%)0.0 V34.97 V (291.45%)2650.3 WDrop/Amp High
3 AWG26.67 mm²100 A16.81 V (140.12%)0.0 V27.74 V (231.13%)2101.8 WDrop/Amp High
2 AWG33.62 mm²115 A13.34 V (111.15%)0.0 V22.0 V (183.35%)1667.3 WDrop/Amp High
1 AWG42.41 mm²130 A10.57 V (88.12%)1.4 V17.44 V (145.35%)1321.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.38 V (69.86%)3.6 V13.83 V (115.24%)1047.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.65 V (55.42%)5.3 V10.97 V (91.42%)831.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.28 V (43.96%)6.7 V8.7 V (72.51%)659.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.18 V (34.86%)7.8 V6.9 V (57.5%)522.9 WDrop/Amp High
250 kcmil126.7 mm²255 A3.54 V (29.49%)8.5 V5.84 V (48.65%)442.4 WDrop/Amp High
300 kcmil152.0 mm²285 A2.95 V (24.59%)9.0 V4.87 V (40.55%)368.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.53 V (21.08%)9.5 V4.17 V (34.77%)316.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.21 V (18.44%)9.8 V3.65 V (30.41%)276.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.77 V (14.75%)10.2 V2.92 V (24.33%)221.2 WDrop/Amp High
600 kcmil304.0 mm²420 A1.48 V (12.29%)10.5 V2.43 V (20.28%)184.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.18 V (9.83%)10.8 V1.95 V (16.22%)147.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.89 V (7.38%)11.1 V1.46 V (12.17%)110.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 275 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.3V (2.46%) and delivers 11.7V at the load.

What size aluminum wire is required for 125 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.46V (12.17%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.