🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)2 AWGDrop: 3.2V (2.67%)
Voltage at Load End116.9 VLoss: 3.08 V (123.4 W)
Power & Breaker (125%)4.8 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A31.36 V (26.13%)88.6 V51.73 V (43.11%)1254.4 WDrop/Amp High
12 AWG3.31 mm²20 A19.71 V (16.42%)100.3 V32.51 V (27.09%)788.2 WDrop/Amp High
10 AWG5.26 mm²30 A12.4 V (10.33%)107.6 V20.46 V (17.05%)496.0 WDrop/Amp High
8 AWG8.37 mm²50 A7.79 V (6.49%)112.2 V12.85 V (10.71%)311.7 WDrop/Amp High
6 AWG13.3 mm²65 A4.9 V (4.09%)115.1 V8.09 V (6.74%)196.2 W~ ≤5%
4 AWG21.15 mm²85 A3.08 V (2.57%)116.9 V5.09 V (4.24%)123.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.45 V (2.04%)117.6 V4.03 V (3.36%)97.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.94 V (1.62%)118.1 V3.2 V (2.67%)77.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.54 V (1.28%)118.5 V2.54 V (2.11%)61.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.22 V (1.02%)118.8 V2.01 V (1.68%)48.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.97 V (0.81%)119.0 V1.6 V (1.33%)38.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.77 V (0.64%)119.2 V1.27 V (1.05%)30.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.61 V (0.51%)119.4 V1.0 V (0.84%)24.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.51 V (0.43%)119.5 V0.85 V (0.71%)20.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.43 V (0.36%)119.6 V0.71 V (0.59%)17.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.37 V (0.31%)119.6 V0.61 V (0.51%)14.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.32 V (0.27%)119.7 V0.53 V (0.44%)12.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.26 V (0.21%)119.7 V0.42 V (0.35%)10.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.21 V (0.18%)119.8 V0.35 V (0.29%)8.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.17 V (0.14%)119.8 V0.28 V (0.24%)6.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.13 V (0.11%)119.9 V0.21 V (0.18%)5.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 125 feet one-way at 120V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 3.08V (2.57%) and delivers 116.9V at the load.

What size aluminum wire is required for 40 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 3.2V (2.67%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.