🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.56%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 3.19V (2.66%)
Voltage at Load End116.9 VLoss: 3.08 V (246.1 W)
Power & Breaker (125%)9.6 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A62.72 V (52.27%)57.3 V103.46 V (86.21%)5017.5 WDrop/Amp High
12 AWG3.31 mm²20 A39.41 V (32.84%)80.6 V65.01 V (54.18%)3153.0 WDrop/Amp High
10 AWG5.26 mm²30 A24.8 V (20.67%)95.2 V40.91 V (34.09%)1984.1 WDrop/Amp High
8 AWG8.37 mm²50 A15.59 V (12.99%)104.4 V25.71 V (21.42%)1246.9 WDrop/Amp High
6 AWG13.3 mm²65 A9.81 V (8.17%)110.2 V16.18 V (13.48%)784.7 WDrop/Amp High
4 AWG21.15 mm²85 A6.17 V (5.14%)113.8 V10.17 V (8.48%)493.4 WDrop/Amp High
3 AWG26.67 mm²100 A4.89 V (4.08%)115.1 V8.07 V (6.72%)391.3 W~ ≤5%
2 AWG33.62 mm²115 A3.88 V (3.23%)116.1 V6.4 V (5.33%)310.4 W~ ≤5%
1 AWG42.41 mm²130 A3.08 V (2.56%)116.9 V5.07 V (4.23%)246.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.44 V (2.03%)117.6 V4.02 V (3.35%)195.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.93 V (1.61%)118.1 V3.19 V (2.66%)154.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.53 V (1.28%)118.5 V2.53 V (2.11%)122.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.22 V (1.01%)118.8 V2.01 V (1.67%)97.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.03 V (0.86%)119.0 V1.7 V (1.42%)82.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.86 V (0.72%)119.1 V1.42 V (1.18%)68.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.74 V (0.61%)119.3 V1.21 V (1.01%)58.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.64 V (0.54%)119.4 V1.06 V (0.88%)51.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.51 V (0.43%)119.5 V0.85 V (0.71%)41.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.43 V (0.36%)119.6 V0.71 V (0.59%)34.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.34 V (0.29%)119.7 V0.57 V (0.47%)27.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.26 V (0.21%)119.7 V0.42 V (0.35%)20.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 125 feet one-way at 120V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 3.08V (2.56%) and delivers 116.9V at the load.

What size aluminum wire is required for 80 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 3.19V (2.66%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.