⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 200 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.42%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.02V (2.51%)
Voltage at Load End234.2 VLoss: 5.8 V (870.6 W)
Power & Breaker (125%)36.0 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A188.16 V (78.4%)51.8 V310.37 V (129.32%)28223.3 WDrop/Amp High
12 AWG3.31 mm²20 A118.24 V (49.27%)121.8 V195.04 V (81.26%)17735.5 WDrop/Amp High
10 AWG5.26 mm²30 A74.4 V (31.0%)165.6 V122.73 V (51.14%)11160.5 WDrop/Amp High
8 AWG8.37 mm²50 A46.76 V (19.48%)193.2 V77.13 V (32.14%)7013.7 WDrop/Amp High
6 AWG13.3 mm²65 A29.43 V (12.26%)210.6 V48.54 V (20.22%)4413.9 WDrop/Amp High
4 AWG21.15 mm²85 A18.5 V (7.71%)221.5 V30.52 V (12.72%)2775.6 WDrop/Amp High
3 AWG26.67 mm²100 A14.67 V (6.11%)225.3 V24.21 V (10.09%)2201.1 WDrop/Amp High
2 AWG33.62 mm²115 A11.64 V (4.85%)228.4 V19.2 V (8.0%)1746.1 WDrop/Amp High
1 AWG42.41 mm²130 A9.23 V (3.85%)230.8 V15.22 V (6.34%)1384.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.32 V (3.05%)232.7 V12.07 V (5.03%)1097.5 W~ ≤5%
2/0 AWG67.43 mm²175 A5.8 V (2.42%)234.2 V9.57 V (3.99%)870.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.6 V (1.92%)235.4 V7.59 V (3.16%)690.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.65 V (1.52%)236.3 V6.02 V (2.51%)547.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.09 V (1.29%)236.9 V5.1 V (2.12%)463.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.57 V (1.07%)237.4 V4.25 V (1.77%)386.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.21 V (0.92%)237.8 V3.64 V (1.52%)331.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.93 V (0.8%)238.1 V3.18 V (1.33%)289.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.54 V (0.64%)238.5 V2.55 V (1.06%)231.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.29 V (0.54%)238.7 V2.12 V (0.88%)193.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.03 V (0.43%)239.0 V1.7 V (0.71%)154.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.77 V (0.32%)239.2 V1.27 V (0.53%)115.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 200 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.8V (2.42%) and delivers 234.2V at the load.

What size aluminum wire is required for 150 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.02V (2.51%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.