🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 200 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.59%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 6.44V (2.68%)
Voltage at Load End233.8 VLoss: 6.21 V (496.7 W)
Power & Breaker (125%)19.2 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A100.35 V (41.81%)139.7 V165.53 V (68.97%)8028.0 WDrop/Amp High
12 AWG3.31 mm²20 A63.06 V (26.27%)176.9 V104.02 V (43.34%)5044.8 WDrop/Amp High
10 AWG5.26 mm²30 A39.68 V (16.53%)200.3 V65.46 V (27.27%)3174.6 WDrop/Amp High
8 AWG8.37 mm²50 A24.94 V (10.39%)215.1 V41.14 V (17.14%)1995.0 WDrop/Amp High
6 AWG13.3 mm²65 A15.69 V (6.54%)224.3 V25.89 V (10.79%)1255.5 WDrop/Amp High
4 AWG21.15 mm²85 A9.87 V (4.11%)230.1 V16.28 V (6.78%)789.5 W~ ≤5%
3 AWG26.67 mm²100 A7.83 V (3.26%)232.2 V12.91 V (5.38%)626.1 W~ ≤5%
2 AWG33.62 mm²115 A6.21 V (2.59%)233.8 V10.24 V (4.27%)496.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.92 V (2.05%)235.1 V8.12 V (3.38%)393.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.9 V (1.63%)236.1 V6.44 V (2.68%)312.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.1 V (1.29%)236.9 V5.11 V (2.13%)247.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.46 V (1.02%)237.5 V4.05 V (1.69%)196.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.95 V (0.81%)238.1 V3.21 V (1.34%)155.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.65 V (0.69%)238.4 V2.72 V (1.13%)131.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.37 V (0.57%)238.6 V2.27 V (0.94%)109.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.18 V (0.49%)238.8 V1.94 V (0.81%)94.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.03 V (0.43%)239.0 V1.7 V (0.71%)82.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.82 V (0.34%)239.2 V1.36 V (0.57%)65.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.69 V (0.29%)239.3 V1.13 V (0.47%)54.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.55 V (0.23%)239.5 V0.91 V (0.38%)43.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.41 V (0.17%)239.6 V0.68 V (0.28%)33.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 200 feet one-way at 240V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 6.21V (2.59%) and delivers 233.8V at the load.

What size aluminum wire is required for 80 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 6.44V (2.68%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.