🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.5V (2.92%)
Voltage at Load End116.5 VLoss: 3.54 V (531.0 W)
Power & Breaker (125%)18.0 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A258.71 V (215.59%)0.0 V426.76 V (355.63%)38807.0 WDrop/Amp High
12 AWG3.31 mm²20 A162.58 V (135.48%)0.0 V268.17 V (223.48%)24386.3 WDrop/Amp High
10 AWG5.26 mm²30 A102.31 V (85.25%)17.7 V168.76 V (140.63%)15345.8 WDrop/Amp High
8 AWG8.37 mm²50 A64.29 V (53.58%)55.7 V106.05 V (88.38%)9643.8 WDrop/Amp High
6 AWG13.3 mm²65 A40.46 V (33.72%)79.5 V66.74 V (55.62%)6069.1 WDrop/Amp High
4 AWG21.15 mm²85 A25.44 V (21.2%)94.6 V41.97 V (34.97%)3816.5 WDrop/Amp High
3 AWG26.67 mm²100 A20.18 V (16.81%)99.8 V33.28 V (27.74%)3026.6 WDrop/Amp High
2 AWG33.62 mm²115 A16.01 V (13.34%)104.0 V26.4 V (22.0%)2400.9 WDrop/Amp High
1 AWG42.41 mm²130 A12.69 V (10.57%)107.3 V20.93 V (17.44%)1903.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.06 V (8.38%)109.9 V16.59 V (13.83%)1509.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.98 V (6.65%)112.0 V13.16 V (10.97%)1197.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.33 V (5.28%)113.7 V10.44 V (8.7%)949.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.02 V (4.18%)115.0 V8.28 V (6.9%)753.0 W~ ≤5%
250 kcmil126.7 mm²255 A4.25 V (3.54%)115.8 V7.01 V (5.84%)637.1 W~ ≤5%
300 kcmil152.0 mm²285 A3.54 V (2.95%)116.5 V5.84 V (4.87%)531.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.04 V (2.53%)117.0 V5.01 V (4.17%)455.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.65 V (2.21%)117.3 V4.38 V (3.65%)398.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.12 V (1.77%)117.9 V3.5 V (2.92%)318.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.77 V (1.48%)118.2 V2.92 V (2.43%)265.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.42 V (1.18%)118.6 V2.34 V (1.95%)212.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.06 V (0.89%)118.9 V1.75 V (1.46%)159.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 275 feet one-way at 120V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.54V (2.95%) and delivers 116.5V at the load.

What size aluminum wire is required for 150 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.5V (2.92%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.