🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)2 AWGDrop: 3.52V (2.93%)
Voltage at Load End116.6 VLoss: 3.39 V (67.8 W)
Power & Breaker (125%)2.4 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A34.5 V (28.75%)85.5 V56.9 V (47.42%)689.9 WDrop/Amp High
12 AWG3.31 mm²20 A21.68 V (18.06%)98.3 V35.76 V (29.8%)433.5 WDrop/Amp High
10 AWG5.26 mm²30 A13.64 V (11.37%)106.4 V22.5 V (18.75%)272.8 WDrop/Amp High
8 AWG8.37 mm²50 A8.57 V (7.14%)111.4 V14.14 V (11.78%)171.4 WDrop/Amp High
6 AWG13.3 mm²65 A5.39 V (4.5%)114.6 V8.9 V (7.42%)107.9 W~ ≤5%
4 AWG21.15 mm²85 A3.39 V (2.83%)116.6 V5.6 V (4.66%)67.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.69 V (2.24%)117.3 V4.44 V (3.7%)53.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.13 V (1.78%)117.9 V3.52 V (2.93%)42.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.69 V (1.41%)118.3 V2.79 V (2.33%)33.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.34 V (1.12%)118.7 V2.21 V (1.84%)26.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.06 V (0.89%)118.9 V1.76 V (1.46%)21.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.84 V (0.7%)119.2 V1.39 V (1.16%)16.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.67 V (0.56%)119.3 V1.1 V (0.92%)13.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.57 V (0.47%)119.4 V0.93 V (0.78%)11.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.47 V (0.39%)119.5 V0.78 V (0.65%)9.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.4 V (0.34%)119.6 V0.67 V (0.56%)8.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.35 V (0.29%)119.6 V0.58 V (0.49%)7.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (0.24%)119.7 V0.47 V (0.39%)5.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.24 V (0.2%)119.8 V0.39 V (0.32%)4.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.16%)119.8 V0.31 V (0.26%)3.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.12%)119.9 V0.23 V (0.19%)2.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 275 feet one-way at 120V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 3.39V (2.83%) and delivers 116.6V at the load.

What size aluminum wire is required for 20 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 3.52V (2.93%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.