🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 30 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 0.4%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 0.99V (0.41%)
Voltage at Load End239.0 VLoss: 0.95 V (246.9 W)
Power & Breaker (125%)62.35 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A24.44 V (10.18%)215.6 V40.32 V (16.8%)6350.2 WDrop/Amp High
12 AWG3.31 mm²20 A15.36 V (6.4%)224.6 V25.34 V (10.56%)3990.5 WDrop/Amp High
10 AWG5.26 mm²30 A9.67 V (4.03%)230.3 V15.94 V (6.64%)2511.1 WDrop/Amp High
8 AWG8.37 mm²50 A6.07 V (2.53%)233.9 V10.02 V (4.17%)1578.1 WDrop/Amp High
6 AWG13.3 mm²65 A3.82 V (1.59%)236.2 V6.31 V (2.63%)993.1 WDrop/Amp High
4 AWG21.15 mm²85 A2.4 V (1.0%)237.6 V3.97 V (1.65%)624.5 WDrop/Amp High
3 AWG26.67 mm²100 A1.91 V (0.79%)238.1 V3.14 V (1.31%)495.3 WDrop/Amp High
2 AWG33.62 mm²115 A1.51 V (0.63%)238.5 V2.49 V (1.04%)392.9 WDrop/Amp High
1 AWG42.41 mm²130 A1.2 V (0.5%)238.8 V1.98 V (0.82%)311.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.95 V (0.4%)239.0 V1.57 V (0.65%)246.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.75 V (0.31%)239.2 V1.24 V (0.52%)195.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.6 V (0.25%)239.4 V0.99 V (0.41%)155.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.47 V (0.2%)239.5 V0.78 V (0.33%)123.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.4 V (0.17%)239.6 V0.66 V (0.28%)104.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.33 V (0.14%)239.7 V0.55 V (0.23%)86.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.29 V (0.12%)239.7 V0.47 V (0.2%)74.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.25 V (0.1%)239.7 V0.41 V (0.17%)65.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.2 V (0.08%)239.8 V0.33 V (0.14%)52.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.17 V (0.07%)239.8 V0.28 V (0.11%)43.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (0.06%)239.9 V0.22 V (0.09%)34.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.04%)239.9 V0.17 V (0.07%)26.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 30 feet one-way at 240V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 0.95V (0.4%) and delivers 239.0V at the load.

What size aluminum wire is required for 150 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 0.99V (0.41%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.