🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 30 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 0.84%
Aluminum Wire (≤3% Drop)6 AWGDrop: 2.1V (0.88%)
Voltage at Load End238.0 VLoss: 2.02 V (175.3 W)
Power & Breaker (125%)20.78 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A8.15 V (3.39%)231.9 V13.44 V (5.6%)705.6 WDrop/Amp High
12 AWG3.31 mm²20 A5.12 V (2.13%)234.9 V8.45 V (3.52%)443.4 WDrop/Amp High
10 AWG5.26 mm²30 A3.22 V (1.34%)236.8 V5.31 V (2.21%)279.0 WDrop/Amp High
8 AWG8.37 mm²50 A2.02 V (0.84%)238.0 V3.34 V (1.39%)175.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.27 V (0.53%)238.7 V2.1 V (0.88%)110.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.8 V (0.33%)239.2 V1.32 V (0.55%)69.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.64 V (0.26%)239.4 V1.05 V (0.44%)55.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.5 V (0.21%)239.5 V0.83 V (0.35%)43.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.4 V (0.17%)239.6 V0.66 V (0.27%)34.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.32 V (0.13%)239.7 V0.52 V (0.22%)27.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.25 V (0.1%)239.7 V0.41 V (0.17%)21.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.2 V (0.08%)239.8 V0.33 V (0.14%)17.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.16 V (0.07%)239.8 V0.26 V (0.11%)13.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.13 V (0.06%)239.9 V0.22 V (0.09%)11.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.11 V (0.05%)239.9 V0.18 V (0.08%)9.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.1 V (0.04%)239.9 V0.16 V (0.07%)8.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.08 V (0.03%)239.9 V0.14 V (0.06%)7.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.07 V (0.03%)239.9 V0.11 V (0.05%)5.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.06 V (0.02%)239.9 V0.09 V (0.04%)4.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.02%)240.0 V0.07 V (0.03%)3.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)240.0 V0.06 V (0.02%)2.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 30 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.02V (0.84%) and delivers 238.0V at the load.

What size aluminum wire is required for 50 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 2.1V (0.88%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.