⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 300 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.76%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 3.19V (2.65%)
Voltage at Load End116.7 VLoss: 3.31 V (496.7 W)
Power & Breaker (125%)18.0 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 300 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A282.23 V (235.19%)0.0 V465.55 V (387.96%)42335.0 WDrop/Amp High
12 AWG3.31 mm²20 A177.35 V (147.8%)0.0 V292.55 V (243.79%)26603.2 WDrop/Amp High
10 AWG5.26 mm²30 A111.61 V (93.0%)8.4 V184.1 V (153.41%)16740.8 WDrop/Amp High
8 AWG8.37 mm²50 A70.14 V (58.45%)49.9 V115.69 V (96.41%)10520.5 WDrop/Amp High
6 AWG13.3 mm²65 A44.14 V (36.78%)75.9 V72.81 V (60.67%)6620.8 WDrop/Amp High
4 AWG21.15 mm²85 A27.76 V (23.13%)92.2 V45.78 V (38.15%)4163.4 WDrop/Amp High
3 AWG26.67 mm²100 A22.01 V (18.34%)98.0 V36.31 V (30.26%)3301.7 WDrop/Amp High
2 AWG33.62 mm²115 A17.46 V (14.55%)102.5 V28.8 V (24.0%)2619.2 WDrop/Amp High
1 AWG42.41 mm²130 A13.84 V (11.54%)106.2 V22.83 V (19.03%)2076.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.97 V (9.15%)109.0 V18.1 V (15.09%)1646.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.71 V (7.25%)111.3 V14.36 V (11.97%)1305.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.91 V (5.75%)113.1 V11.39 V (9.49%)1035.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.48 V (4.56%)114.5 V9.03 V (7.53%)821.4 W~ ≤5%
250 kcmil126.7 mm²255 A4.63 V (3.86%)115.4 V7.64 V (6.37%)695.0 W~ ≤5%
300 kcmil152.0 mm²285 A3.86 V (3.22%)116.1 V6.37 V (5.31%)579.3 W~ ≤5%
350 kcmil177.3 mm²310 A3.31 V (2.76%)116.7 V5.46 V (4.55%)496.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.9 V (2.41%)117.1 V4.78 V (3.98%)434.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.32 V (1.93%)117.7 V3.82 V (3.18%)347.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.93 V (1.61%)118.1 V3.19 V (2.65%)289.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.54 V (1.29%)118.5 V2.55 V (2.12%)231.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.16 V (0.97%)118.8 V1.91 V (1.59%)173.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 300 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 300 feet one-way at 120V (1-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 3.31V (2.76%) and delivers 116.7V at the load.

What size aluminum wire is required for 150 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 3.19V (2.65%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.