⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.91%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.44V (2.68%)
Voltage at Load End233.0 VLoss: 6.98 V (1812.7 W)
Power & Breaker (125%)62.35 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A285.16 V (118.82%)0.0 V470.38 V (195.99%)74086.2 WDrop/Amp High
12 AWG3.31 mm²20 A179.19 V (74.66%)60.8 V295.58 V (123.16%)46555.7 WDrop/Amp High
10 AWG5.26 mm²30 A112.76 V (46.98%)127.2 V186.0 V (77.5%)29296.4 WDrop/Amp High
8 AWG8.37 mm²50 A70.86 V (29.53%)169.1 V116.89 V (48.7%)18410.9 WDrop/Amp High
6 AWG13.3 mm²65 A44.6 V (18.58%)195.4 V73.56 V (30.65%)11586.4 WDrop/Amp High
4 AWG21.15 mm²85 A28.04 V (11.68%)212.0 V46.26 V (19.27%)7286.0 WDrop/Amp High
3 AWG26.67 mm²100 A22.24 V (9.27%)217.8 V36.68 V (15.29%)5778.0 WDrop/Amp High
2 AWG33.62 mm²115 A17.64 V (7.35%)222.4 V29.1 V (12.13%)4583.6 WDrop/Amp High
1 AWG42.41 mm²130 A13.99 V (5.83%)226.0 V23.07 V (9.61%)3633.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.09 V (4.62%)228.9 V18.29 V (7.62%)2880.9 W~ ≤5%
2/0 AWG67.43 mm²175 A8.8 V (3.67%)231.2 V14.51 V (6.05%)2285.3 W~ ≤5%
3/0 AWG85.01 mm²200 A6.98 V (2.91%)233.0 V11.51 V (4.8%)1812.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.53 V (2.31%)234.5 V9.13 V (3.8%)1437.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.68 V (1.95%)235.3 V7.72 V (3.22%)1216.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.9 V (1.63%)236.1 V6.44 V (2.68%)1013.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.35 V (1.39%)236.7 V5.52 V (2.3%)869.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.93 V (1.22%)237.1 V4.83 V (2.01%)760.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.34 V (0.98%)237.7 V3.86 V (1.61%)608.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.95 V (0.81%)238.0 V3.22 V (1.34%)506.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.56 V (0.65%)238.4 V2.57 V (1.07%)405.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.17 V (0.49%)238.8 V1.93 V (0.8%)304.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 350 feet one-way at 240V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 6.98V (2.91%) and delivers 233.0V at the load.

What size aluminum wire is required for 150 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.44V (2.68%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.