🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.56%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 5.53V (2.66%)
Voltage at Load End202.7 VLoss: 5.33 V (184.6 W)
Power & Breaker (125%)7.21 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A108.63 V (52.23%)99.4 V179.19 V (86.15%)3763.1 WDrop/Amp High
12 AWG3.31 mm²20 A68.26 V (32.82%)139.7 V112.6 V (54.14%)2364.7 WDrop/Amp High
10 AWG5.26 mm²30 A42.96 V (20.65%)165.0 V70.86 V (34.07%)1488.1 WDrop/Amp High
8 AWG8.37 mm²50 A27.0 V (12.98%)181.0 V44.53 V (21.41%)935.2 WDrop/Amp High
6 AWG13.3 mm²65 A16.99 V (8.17%)191.0 V28.02 V (13.47%)588.5 WDrop/Amp High
4 AWG21.15 mm²85 A10.68 V (5.14%)197.3 V17.62 V (8.47%)370.1 WDrop/Amp High
3 AWG26.67 mm²100 A8.47 V (4.07%)199.5 V13.98 V (6.72%)293.5 W~ ≤5%
2 AWG33.62 mm²115 A6.72 V (3.23%)201.3 V11.09 V (5.33%)232.8 W~ ≤5%
1 AWG42.41 mm²130 A5.33 V (2.56%)202.7 V8.79 V (4.23%)184.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.22 V (2.03%)203.8 V6.97 V (3.35%)146.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.35 V (1.61%)204.6 V5.53 V (2.66%)116.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.66 V (1.28%)205.3 V4.38 V (2.11%)92.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.11 V (1.01%)205.9 V3.48 V (1.67%)73.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.78 V (0.86%)206.2 V2.94 V (1.41%)61.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.49 V (0.71%)206.5 V2.45 V (1.18%)51.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.27 V (0.61%)206.7 V2.1 V (1.01%)44.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.11 V (0.54%)206.9 V1.84 V (0.88%)38.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.89 V (0.43%)207.1 V1.47 V (0.71%)30.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.74 V (0.36%)207.3 V1.23 V (0.59%)25.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.59 V (0.29%)207.4 V0.98 V (0.47%)20.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.45 V (0.21%)207.6 V0.74 V (0.35%)15.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 1000 feet one-way at 208V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 5.33V (2.56%) and delivers 202.7V at the load.

What size aluminum wire is required for 20 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 5.53V (2.66%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.