🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.71V (7.07%)
Voltage at Load End203.5 VLoss: 4.46 V (3089.5 W)
Power & Breaker (125%)144.11 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2172.63 V (1044.53%)0.0 V3583.83 V (1722.99%)1505243.1 WDrop/Amp High
12 AWG3.31 mm²20 A1365.28 V (656.38%)0.0 V2252.07 V (1082.73%)945892.9 WDrop/Amp High
10 AWG5.26 mm²30 A859.14 V (413.05%)0.0 V1417.18 V (681.34%)595229.2 WDrop/Amp High
8 AWG8.37 mm²50 A539.91 V (259.57%)0.0 V890.6 V (428.18%)374062.8 WDrop/Amp High
6 AWG13.3 mm²65 A339.78 V (163.36%)0.0 V560.48 V (269.46%)235406.4 WDrop/Amp High
4 AWG21.15 mm²85 A213.67 V (102.72%)0.0 V352.45 V (169.45%)148033.4 WDrop/Amp High
3 AWG26.67 mm²100 A169.44 V (81.46%)38.6 V279.5 V (134.38%)117394.3 WDrop/Amp High
2 AWG33.62 mm²115 A134.42 V (64.62%)73.6 V221.72 V (106.6%)93126.3 WDrop/Amp High
1 AWG42.41 mm²130 A106.56 V (51.23%)101.4 V175.77 V (84.5%)73824.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A84.48 V (40.62%)123.5 V139.36 V (67.0%)58532.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A67.02 V (32.22%)141.0 V110.55 V (53.15%)46431.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A53.16 V (25.56%)154.8 V87.69 V (42.16%)36829.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A42.16 V (20.27%)165.8 V69.54 V (33.43%)29206.2 WDrop/Amp High
250 kcmil126.7 mm²255 A35.67 V (17.15%)172.3 V58.83 V (28.29%)24711.2 WDrop/Amp High
300 kcmil152.0 mm²285 A29.73 V (14.29%)178.3 V49.04 V (23.58%)20598.1 WDrop/Amp High
350 kcmil177.3 mm²310 A25.49 V (12.25%)182.5 V42.04 V (20.21%)17658.8 WDrop/Amp High
400 kcmil202.7 mm²335 A22.29 V (10.72%)185.7 V36.78 V (17.68%)15446.0 WDrop/Amp High
500 kcmil253.4 mm²380 A17.83 V (8.57%)190.2 V29.42 V (14.14%)12355.6 WDrop/Amp High
600 kcmil304.0 mm²420 A14.87 V (7.15%)193.1 V24.52 V (11.79%)10299.0 WDrop/Amp High
750 kcmil380.0 mm²475 A11.89 V (5.72%)196.1 V19.62 V (9.43%)8239.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.92 V (4.29%)199.1 V14.71 V (7.07%)6179.0 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 1000 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.46V (2.15%) and delivers 203.5V at the load.

What size aluminum wire is required for 400 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.71V (7.07%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.