🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 40 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.59%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 0.32V (2.68%)
Voltage at Load End11.7 VLoss: 0.31 V (6.2 W)
Power & Breaker (125%)0.24 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 40 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A5.02 V (41.81%)7.0 V8.28 V (68.97%)100.3 WDrop/Amp High
12 AWG3.31 mm²20 A3.15 V (26.27%)8.8 V5.2 V (43.34%)63.1 WDrop/Amp High
10 AWG5.26 mm²30 A1.98 V (16.53%)10.0 V3.27 V (27.27%)39.7 WDrop/Amp High
8 AWG8.37 mm²50 A1.25 V (10.39%)10.8 V2.06 V (17.14%)24.9 WDrop/Amp High
6 AWG13.3 mm²65 A0.78 V (6.54%)11.2 V1.29 V (10.79%)15.7 WDrop/Amp High
4 AWG21.15 mm²85 A0.49 V (4.11%)11.5 V0.81 V (6.78%)9.9 W~ ≤5%
3 AWG26.67 mm²100 A0.39 V (3.26%)11.6 V0.65 V (5.38%)7.8 W~ ≤5%
2 AWG33.62 mm²115 A0.31 V (2.59%)11.7 V0.51 V (4.27%)6.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.25 V (2.05%)11.8 V0.41 V (3.38%)4.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.2 V (1.63%)11.8 V0.32 V (2.68%)3.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.15 V (1.29%)11.8 V0.26 V (2.13%)3.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.12 V (1.02%)11.9 V0.2 V (1.69%)2.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.1 V (0.81%)11.9 V0.16 V (1.34%)1.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.08 V (0.69%)11.9 V0.14 V (1.13%)1.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.07 V (0.57%)11.9 V0.11 V (0.94%)1.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.06 V (0.49%)11.9 V0.1 V (0.81%)1.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.05 V (0.43%)11.9 V0.08 V (0.71%)1.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.04 V (0.34%)12.0 V0.07 V (0.57%)0.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.29%)12.0 V0.06 V (0.47%)0.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.23%)12.0 V0.05 V (0.38%)0.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.17%)12.0 V0.03 V (0.28%)0.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 40 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 40 feet one-way at 12V (DC), you need 2 AWG copper wire. This produces a voltage drop of 0.31V (2.59%) and delivers 11.7V at the load.

What size aluminum wire is required for 20 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 0.32V (2.68%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.