🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 40 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.75%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 0.34V (2.83%)
Voltage at Load End11.7 VLoss: 0.33 V (26.4 W)
Power & Breaker (125%)0.96 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 40 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A20.07 V (167.25%)0.0 V33.11 V (275.88%)1605.6 WDrop/Amp High
12 AWG3.31 mm²20 A12.61 V (105.1%)0.0 V20.8 V (173.36%)1009.0 WDrop/Amp High
10 AWG5.26 mm²30 A7.94 V (66.14%)4.1 V13.09 V (109.09%)634.9 WDrop/Amp High
8 AWG8.37 mm²50 A4.99 V (41.56%)7.0 V8.23 V (68.56%)399.0 WDrop/Amp High
6 AWG13.3 mm²65 A3.14 V (26.16%)8.9 V5.18 V (43.15%)251.1 WDrop/Amp High
4 AWG21.15 mm²85 A1.97 V (16.45%)10.0 V3.26 V (27.13%)157.9 WDrop/Amp High
3 AWG26.67 mm²100 A1.57 V (13.04%)10.4 V2.58 V (21.52%)125.2 WDrop/Amp High
2 AWG33.62 mm²115 A1.24 V (10.35%)10.8 V2.05 V (17.07%)99.3 WDrop/Amp High
1 AWG42.41 mm²130 A0.98 V (8.2%)11.0 V1.62 V (13.53%)78.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.78 V (6.5%)11.2 V1.29 V (10.73%)62.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.62 V (5.16%)11.4 V1.02 V (8.51%)49.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.49 V (4.09%)11.5 V0.81 V (6.75%)39.3 W~ ≤5%
4/0 AWG107.2 mm²230 A0.39 V (3.25%)11.6 V0.64 V (5.35%)31.2 W~ ≤5%
250 kcmil126.7 mm²255 A0.33 V (2.75%)11.7 V0.54 V (4.53%)26.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.27 V (2.29%)11.7 V0.45 V (3.78%)22.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.24 V (1.96%)11.8 V0.39 V (3.24%)18.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.21 V (1.72%)11.8 V0.34 V (2.83%)16.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (1.37%)11.8 V0.27 V (2.26%)13.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (1.14%)11.9 V0.23 V (1.89%)11.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.92%)11.9 V0.18 V (1.51%)8.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.69%)11.9 V0.14 V (1.13%)6.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 40 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 40 feet one-way at 12V (DC), you need 250 kcmil copper wire. This produces a voltage drop of 0.33V (2.75%) and delivers 11.7V at the load.

What size aluminum wire is required for 80 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 0.34V (2.83%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.