⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.45%
Aluminum Wire (≤3% Drop)1 AWGDrop: 0.3V (2.54%)
Voltage at Load End11.7 VLoss: 0.29 V (5.9 W)
Power & Breaker (125%)0.24 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3.76 V (31.36%)8.2 V6.21 V (51.73%)75.3 WDrop/Amp High
12 AWG3.31 mm²20 A2.36 V (19.71%)9.6 V3.9 V (32.51%)47.3 WDrop/Amp High
10 AWG5.26 mm²30 A1.49 V (12.4%)10.5 V2.45 V (20.46%)29.8 WDrop/Amp High
8 AWG8.37 mm²50 A0.94 V (7.79%)11.1 V1.54 V (12.85%)18.7 WDrop/Amp High
6 AWG13.3 mm²65 A0.59 V (4.9%)11.4 V0.97 V (8.09%)11.8 W~ ≤5%
4 AWG21.15 mm²85 A0.37 V (3.08%)11.6 V0.61 V (5.09%)7.4 W~ ≤5%
3 AWG26.67 mm²100 A0.29 V (2.45%)11.7 V0.48 V (4.03%)5.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.23 V (1.94%)11.8 V0.38 V (3.2%)4.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.18 V (1.54%)11.8 V0.3 V (2.54%)3.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.15 V (1.22%)11.9 V0.24 V (2.01%)2.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.12 V (0.97%)11.9 V0.19 V (1.6%)2.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.09 V (0.77%)11.9 V0.15 V (1.27%)1.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.07 V (0.61%)11.9 V0.12 V (1.0%)1.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.06 V (0.51%)11.9 V0.1 V (0.85%)1.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.05 V (0.43%)11.9 V0.08 V (0.71%)1.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.04 V (0.37%)12.0 V0.07 V (0.61%)0.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.04 V (0.32%)12.0 V0.06 V (0.53%)0.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.03 V (0.26%)12.0 V0.05 V (0.42%)0.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.21%)12.0 V0.04 V (0.35%)0.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.02 V (0.17%)12.0 V0.03 V (0.28%)0.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.13%)12.0 V0.03 V (0.21%)0.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 30 feet one-way at 12V (DC), you need 3 AWG copper wire. This produces a voltage drop of 0.29V (2.45%) and delivers 11.7V at the load.

What size aluminum wire is required for 20 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 0.3V (2.54%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.