🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 80 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 2.63%
Aluminum Wire (≤3% Drop)10 AWGDrop: 6.55V (2.73%)
Voltage at Load End233.7 VLoss: 6.31 V (126.1 W)
Power & Breaker (125%)4.8 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A10.03 V (4.18%)230.0 V16.55 V (6.9%)200.7 WDrop/Amp High
12 AWG3.31 mm²20 A6.31 V (2.63%)233.7 V10.4 V (4.33%)126.1 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A3.97 V (1.65%)236.0 V6.55 V (2.73%)79.4 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.49 V (1.04%)237.5 V4.11 V (1.71%)49.9 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.57 V (0.65%)238.4 V2.59 V (1.08%)31.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.99 V (0.41%)239.0 V1.63 V (0.68%)19.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.78 V (0.33%)239.2 V1.29 V (0.54%)15.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.62 V (0.26%)239.4 V1.02 V (0.43%)12.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.49 V (0.21%)239.5 V0.81 V (0.34%)9.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.39 V (0.16%)239.6 V0.64 V (0.27%)7.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.31 V (0.13%)239.7 V0.51 V (0.21%)6.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.25 V (0.1%)239.8 V0.41 V (0.17%)4.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.19 V (0.08%)239.8 V0.32 V (0.13%)3.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.16 V (0.07%)239.8 V0.27 V (0.11%)3.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.14 V (0.06%)239.9 V0.23 V (0.09%)2.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.12 V (0.05%)239.9 V0.19 V (0.08%)2.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.1 V (0.04%)239.9 V0.17 V (0.07%)2.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.08 V (0.03%)239.9 V0.14 V (0.06%)1.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.07 V (0.03%)239.9 V0.11 V (0.05%)1.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.02%)239.9 V0.09 V (0.04%)1.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.02%)240.0 V0.07 V (0.03%)0.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 80 feet one-way at 240V (1-Phase), you need 12 AWG copper wire. This produces a voltage drop of 6.31V (2.63%) and delivers 233.7V at the load.

What size aluminum wire is required for 20 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 6.55V (2.73%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.