⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 80 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 1.64%
Aluminum Wire (≤3% Drop)2 AWGDrop: 4.1V (1.71%)
Voltage at Load End236.1 VLoss: 3.95 V (315.8 W)
Power & Breaker (125%)19.2 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A40.14 V (16.72%)199.9 V66.21 V (27.59%)3211.2 WDrop/Amp High
12 AWG3.31 mm²20 A25.22 V (10.51%)214.8 V41.61 V (17.34%)2017.9 WDrop/Amp High
10 AWG5.26 mm²30 A15.87 V (6.61%)224.1 V26.18 V (10.91%)1269.8 WDrop/Amp High
8 AWG8.37 mm²50 A9.98 V (4.16%)230.0 V16.45 V (6.86%)798.0 WDrop/Amp High
6 AWG13.3 mm²65 A6.28 V (2.62%)233.7 V10.35 V (4.31%)502.2 WDrop/Amp High
4 AWG21.15 mm²85 A3.95 V (1.64%)236.1 V6.51 V (2.71%)315.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.13 V (1.3%)236.9 V5.16 V (2.15%)250.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.48 V (1.03%)237.5 V4.1 V (1.71%)198.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.97 V (0.82%)238.0 V3.25 V (1.35%)157.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.56 V (0.65%)238.4 V2.57 V (1.07%)124.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.24 V (0.52%)238.8 V2.04 V (0.85%)99.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.98 V (0.41%)239.0 V1.62 V (0.68%)78.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.78 V (0.32%)239.2 V1.28 V (0.54%)62.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.66 V (0.27%)239.3 V1.09 V (0.45%)52.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.55 V (0.23%)239.5 V0.91 V (0.38%)43.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.47 V (0.2%)239.5 V0.78 V (0.32%)37.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.41 V (0.17%)239.6 V0.68 V (0.28%)33.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.33 V (0.14%)239.7 V0.54 V (0.23%)26.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.27 V (0.11%)239.7 V0.45 V (0.19%)22.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.22 V (0.09%)239.8 V0.36 V (0.15%)17.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.16 V (0.07%)239.8 V0.27 V (0.11%)13.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 80 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 3.95V (1.64%) and delivers 236.1V at the load.

What size aluminum wire is required for 80 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 4.1V (1.71%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.