🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 80 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 1.14%
Aluminum Wire (≤3% Drop)10 AWGDrop: 5.67V (1.18%)
Voltage at Load End474.5 VLoss: 5.46 V (189.2 W)
Power & Breaker (125%)16.63 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 80 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A8.69 V (1.81%)471.3 V14.34 V (2.99%)301.0 WDrop/Amp High
12 AWG3.31 mm²20 A5.46 V (1.14%)474.5 V9.01 V (1.88%)189.2 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A3.44 V (0.72%)476.6 V5.67 V (1.18%)119.0 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.16 V (0.45%)477.8 V3.56 V (0.74%)74.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.36 V (0.28%)478.6 V2.24 V (0.47%)47.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.85 V (0.18%)479.1 V1.41 V (0.29%)29.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.68 V (0.14%)479.3 V1.12 V (0.23%)23.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.54 V (0.11%)479.5 V0.89 V (0.18%)18.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.43 V (0.09%)479.6 V0.7 V (0.15%)14.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.34 V (0.07%)479.7 V0.56 V (0.12%)11.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.27 V (0.06%)479.7 V0.44 V (0.09%)9.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.21 V (0.04%)479.8 V0.35 V (0.07%)7.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.17 V (0.04%)479.8 V0.28 V (0.06%)5.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.14 V (0.03%)479.9 V0.24 V (0.05%)4.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.12 V (0.02%)479.9 V0.2 V (0.04%)4.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.1 V (0.02%)479.9 V0.17 V (0.04%)3.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.09 V (0.02%)479.9 V0.15 V (0.03%)3.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.07 V (0.01%)479.9 V0.12 V (0.02%)2.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.06 V (0.01%)479.9 V0.1 V (0.02%)2.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.01%)480.0 V0.08 V (0.02%)1.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.01%)480.0 V0.06 V (0.01%)1.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 80 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 80 feet one-way at 480V (3-Phase), you need 12 AWG copper wire. This produces a voltage drop of 5.46V (1.14%) and delivers 474.5V at the load.

What size aluminum wire is required for 20 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 5.67V (1.18%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.