🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 80 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.71%
Aluminum Wire (≤3% Drop)2 AWGDrop: 3.55V (0.74%)
Voltage at Load End476.6 VLoss: 3.42 V (473.7 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 80 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A34.76 V (7.24%)445.2 V57.34 V (11.95%)4816.8 WDrop/Amp High
12 AWG3.31 mm²20 A21.84 V (4.55%)458.2 V36.03 V (7.51%)3026.9 WDrop/Amp High
10 AWG5.26 mm²30 A13.75 V (2.86%)466.3 V22.67 V (4.72%)1904.7 WDrop/Amp High
8 AWG8.37 mm²50 A8.64 V (1.8%)471.4 V14.25 V (2.97%)1197.0 WDrop/Amp High
6 AWG13.3 mm²65 A5.44 V (1.13%)474.6 V8.97 V (1.87%)753.3 WDrop/Amp High
4 AWG21.15 mm²85 A3.42 V (0.71%)476.6 V5.64 V (1.17%)473.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.71 V (0.56%)477.3 V4.47 V (0.93%)375.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.15 V (0.45%)477.8 V3.55 V (0.74%)298.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.7 V (0.36%)478.3 V2.81 V (0.59%)236.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.35 V (0.28%)478.6 V2.23 V (0.46%)187.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.07 V (0.22%)478.9 V1.77 V (0.37%)148.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.85 V (0.18%)479.1 V1.4 V (0.29%)117.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.67 V (0.14%)479.3 V1.11 V (0.23%)93.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.57 V (0.12%)479.4 V0.94 V (0.2%)79.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.48 V (0.1%)479.5 V0.78 V (0.16%)65.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.41 V (0.08%)479.6 V0.67 V (0.14%)56.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.36 V (0.07%)479.6 V0.59 V (0.12%)49.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.29 V (0.06%)479.7 V0.47 V (0.1%)39.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.24 V (0.05%)479.8 V0.39 V (0.08%)33.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.04%)479.8 V0.31 V (0.07%)26.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.03%)479.9 V0.24 V (0.05%)19.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 80 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 80 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 3.42V (0.71%) and delivers 476.6V at the load.

What size aluminum wire is required for 80 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 3.55V (0.74%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.