⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 80 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.12%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.6V (1.17%)
Voltage at Load End474.6 VLoss: 5.4 V (467.6 W)
Power & Breaker (125%)41.57 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 80 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A21.73 V (4.53%)458.3 V35.84 V (7.47%)1881.6 WDrop/Amp High
12 AWG3.31 mm²20 A13.65 V (2.84%)466.3 V22.52 V (4.69%)1182.4 WDrop/Amp High
10 AWG5.26 mm²30 A8.59 V (1.79%)471.4 V14.17 V (2.95%)744.0 WDrop/Amp High
8 AWG8.37 mm²50 A5.4 V (1.12%)474.6 V8.91 V (1.86%)467.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.4 V (0.71%)476.6 V5.6 V (1.17%)294.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.14 V (0.45%)477.9 V3.52 V (0.73%)185.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.69 V (0.35%)478.3 V2.8 V (0.58%)146.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.34 V (0.28%)478.7 V2.22 V (0.46%)116.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.07 V (0.22%)478.9 V1.76 V (0.37%)92.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.84 V (0.18%)479.2 V1.39 V (0.29%)73.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.67 V (0.14%)479.3 V1.11 V (0.23%)58.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.53 V (0.11%)479.5 V0.88 V (0.18%)46.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.42 V (0.09%)479.6 V0.7 V (0.14%)36.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.36 V (0.07%)479.6 V0.59 V (0.12%)30.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.3 V (0.06%)479.7 V0.49 V (0.1%)25.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.25 V (0.05%)479.7 V0.42 V (0.09%)22.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.22 V (0.05%)479.8 V0.37 V (0.08%)19.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.18 V (0.04%)479.8 V0.29 V (0.06%)15.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (0.03%)479.9 V0.25 V (0.05%)12.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.02%)479.9 V0.2 V (0.04%)10.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.02%)479.9 V0.15 V (0.03%)7.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 80 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 80 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 5.4V (1.12%) and delivers 474.6V at the load.

What size aluminum wire is required for 50 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.6V (1.17%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.