⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 60 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.68%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 1.91V (0.8%)
Voltage at Load End238.4 VLoss: 1.64 V (369.6 W)
Power & Breaker (125%)54.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A84.67 V (35.28%)155.3 V139.67 V (58.19%)19050.7 WDrop/Amp High
12 AWG3.31 mm²20 A53.21 V (22.17%)186.8 V87.77 V (36.57%)11971.5 WDrop/Amp High
10 AWG5.26 mm²30 A33.48 V (13.95%)206.5 V55.23 V (23.01%)7533.4 WDrop/Amp High
8 AWG8.37 mm²50 A21.04 V (8.77%)219.0 V34.71 V (14.46%)4734.2 WDrop/Amp High
6 AWG13.3 mm²65 A13.24 V (5.52%)226.8 V21.84 V (9.1%)2979.4 WDrop/Amp High
4 AWG21.15 mm²85 A8.33 V (3.47%)231.7 V13.74 V (5.72%)1873.5 WDrop/Amp High
3 AWG26.67 mm²100 A6.6 V (2.75%)233.4 V10.89 V (4.54%)1485.8 WDrop/Amp High
2 AWG33.62 mm²115 A5.24 V (2.18%)234.8 V8.64 V (3.6%)1178.6 WDrop/Amp High
1 AWG42.41 mm²130 A4.15 V (1.73%)235.8 V6.85 V (2.85%)934.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.29 V (1.37%)236.7 V5.43 V (2.26%)740.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.61 V (1.09%)237.4 V4.31 V (1.8%)587.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.07 V (0.86%)237.9 V3.42 V (1.42%)466.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.64 V (0.68%)238.4 V2.71 V (1.13%)369.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.39 V (0.58%)238.6 V2.29 V (0.96%)312.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.16 V (0.48%)238.8 V1.91 V (0.8%)260.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.99 V (0.41%)239.0 V1.64 V (0.68%)223.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.87 V (0.36%)239.1 V1.43 V (0.6%)195.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.7 V (0.29%)239.3 V1.15 V (0.48%)156.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.58 V (0.24%)239.4 V0.96 V (0.4%)130.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.46 V (0.19%)239.5 V0.76 V (0.32%)104.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.35 V (0.14%)239.7 V0.57 V (0.24%)78.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 60 feet one-way at 240V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 1.64V (0.68%) and delivers 238.4V at the load.

What size aluminum wire is required for 225 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 1.91V (0.8%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.