⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.34%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 0.96V (0.4%)
Voltage at Load End239.2 VLoss: 0.82 V (184.8 W)
Power & Breaker (125%)54.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A42.33 V (17.64%)197.7 V69.83 V (29.1%)9525.4 WDrop/Amp High
12 AWG3.31 mm²20 A26.6 V (11.08%)213.4 V43.88 V (18.28%)5985.7 WDrop/Amp High
10 AWG5.26 mm²30 A16.74 V (6.98%)223.3 V27.61 V (11.51%)3766.7 WDrop/Amp High
8 AWG8.37 mm²50 A10.52 V (4.38%)229.5 V17.35 V (7.23%)2367.1 WDrop/Amp High
6 AWG13.3 mm²65 A6.62 V (2.76%)233.4 V10.92 V (4.55%)1489.7 WDrop/Amp High
4 AWG21.15 mm²85 A4.16 V (1.73%)235.8 V6.87 V (2.86%)936.8 WDrop/Amp High
3 AWG26.67 mm²100 A3.3 V (1.38%)236.7 V5.45 V (2.27%)742.9 WDrop/Amp High
2 AWG33.62 mm²115 A2.62 V (1.09%)237.4 V4.32 V (1.8%)589.3 WDrop/Amp High
1 AWG42.41 mm²130 A2.08 V (0.87%)237.9 V3.42 V (1.43%)467.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.65 V (0.69%)238.4 V2.72 V (1.13%)370.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.31 V (0.54%)238.7 V2.15 V (0.9%)293.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.04 V (0.43%)239.0 V1.71 V (0.71%)233.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.82 V (0.34%)239.2 V1.35 V (0.56%)184.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.7 V (0.29%)239.3 V1.15 V (0.48%)156.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.58 V (0.24%)239.4 V0.96 V (0.4%)130.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.5 V (0.21%)239.5 V0.82 V (0.34%)111.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.43 V (0.18%)239.6 V0.72 V (0.3%)97.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.35 V (0.14%)239.7 V0.57 V (0.24%)78.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.29 V (0.12%)239.7 V0.48 V (0.2%)65.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.23 V (0.1%)239.8 V0.38 V (0.16%)52.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (0.07%)239.8 V0.29 V (0.12%)39.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 30 feet one-way at 240V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 0.82V (0.34%) and delivers 239.2V at the load.

What size aluminum wire is required for 225 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 0.96V (0.4%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.