⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 60 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 0.77%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 2.04V (0.85%)
Voltage at Load End238.2 VLoss: 1.84 V (368.3 W)
Power & Breaker (125%)48.0 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A75.26 V (31.36%)164.7 V124.15 V (51.73%)15052.4 WDrop/Amp High
12 AWG3.31 mm²20 A47.29 V (19.71%)192.7 V78.01 V (32.51%)9458.9 WDrop/Amp High
10 AWG5.26 mm²30 A29.76 V (12.4%)210.2 V49.09 V (20.46%)5952.3 WDrop/Amp High
8 AWG8.37 mm²50 A18.7 V (7.79%)221.3 V30.85 V (12.85%)3740.6 WDrop/Amp High
6 AWG13.3 mm²65 A11.77 V (4.9%)228.2 V19.42 V (8.09%)2354.1 WDrop/Amp High
4 AWG21.15 mm²85 A7.4 V (3.08%)232.6 V12.21 V (5.09%)1480.3 WDrop/Amp High
3 AWG26.67 mm²100 A5.87 V (2.45%)234.1 V9.68 V (4.03%)1173.9 WDrop/Amp High
2 AWG33.62 mm²115 A4.66 V (1.94%)235.3 V7.68 V (3.2%)931.3 WDrop/Amp High
1 AWG42.41 mm²130 A3.69 V (1.54%)236.3 V6.09 V (2.54%)738.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.93 V (1.22%)237.1 V4.83 V (2.01%)585.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.32 V (0.97%)237.7 V3.83 V (1.6%)464.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.84 V (0.77%)238.2 V3.04 V (1.27%)368.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.46 V (0.61%)238.5 V2.41 V (1.0%)292.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.24 V (0.51%)238.8 V2.04 V (0.85%)247.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.03 V (0.43%)239.0 V1.7 V (0.71%)206.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.88 V (0.37%)239.1 V1.46 V (0.61%)176.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.77 V (0.32%)239.2 V1.27 V (0.53%)154.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.62 V (0.26%)239.4 V1.02 V (0.42%)123.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.51 V (0.21%)239.5 V0.85 V (0.35%)103.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.41 V (0.17%)239.6 V0.68 V (0.28%)82.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.31 V (0.13%)239.7 V0.51 V (0.21%)61.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 60 feet one-way at 240V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 1.84V (0.77%) and delivers 238.2V at the load.

What size aluminum wire is required for 200 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 2.04V (0.85%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.