🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 250 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)4 AWGDrop: 5.51V (2.65%)
Voltage at Load End202.7 VLoss: 5.31 V (229.9 W)
Power & Breaker (125%)9.01 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 250 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A33.95 V (16.32%)174.1 V56.0 V (26.92%)1470.0 WDrop/Amp High
12 AWG3.31 mm²20 A21.33 V (10.26%)186.7 V35.19 V (16.92%)923.7 WDrop/Amp High
10 AWG5.26 mm²30 A13.42 V (6.45%)194.6 V22.14 V (10.65%)581.3 WDrop/Amp High
8 AWG8.37 mm²50 A8.44 V (4.06%)199.6 V13.92 V (6.69%)365.3 W~ ≤5%
6 AWG13.3 mm²65 A5.31 V (2.55%)202.7 V8.76 V (4.21%)229.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.34 V (1.61%)204.7 V5.51 V (2.65%)144.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.65 V (1.27%)205.4 V4.37 V (2.1%)114.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.1 V (1.01%)205.9 V3.46 V (1.67%)90.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.66 V (0.8%)206.3 V2.75 V (1.32%)72.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.32 V (0.63%)206.7 V2.18 V (1.05%)57.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.05 V (0.5%)207.0 V1.73 V (0.83%)45.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.83 V (0.4%)207.2 V1.37 V (0.66%)36.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.66 V (0.32%)207.3 V1.09 V (0.52%)28.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.56 V (0.27%)207.4 V0.92 V (0.44%)24.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.46 V (0.22%)207.5 V0.77 V (0.37%)20.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.4 V (0.19%)207.6 V0.66 V (0.32%)17.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.35 V (0.17%)207.7 V0.57 V (0.28%)15.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (0.13%)207.7 V0.46 V (0.22%)12.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.11%)207.8 V0.38 V (0.18%)10.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.09%)207.8 V0.31 V (0.15%)8.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.07%)207.9 V0.23 V (0.11%)6.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 250 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 250 feet one-way at 208V (3-Phase), you need 6 AWG copper wire. This produces a voltage drop of 5.31V (2.55%) and delivers 202.7V at the load.

What size aluminum wire is required for 25 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 5.51V (2.65%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.