🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 250 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.21%
Aluminum Wire (≤3% Drop)4 AWGDrop: 5.51V (2.29%)
Voltage at Load End234.7 VLoss: 5.31 V (229.9 W)
Power & Breaker (125%)10.39 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A33.95 V (14.14%)206.1 V56.0 V (23.33%)1470.0 WDrop/Amp High
12 AWG3.31 mm²20 A21.33 V (8.89%)218.7 V35.19 V (14.66%)923.7 WDrop/Amp High
10 AWG5.26 mm²30 A13.42 V (5.59%)226.6 V22.14 V (9.23%)581.3 WDrop/Amp High
8 AWG8.37 mm²50 A8.44 V (3.52%)231.6 V13.92 V (5.8%)365.3 W~ ≤5%
6 AWG13.3 mm²65 A5.31 V (2.21%)234.7 V8.76 V (3.65%)229.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.34 V (1.39%)236.7 V5.51 V (2.29%)144.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.65 V (1.1%)237.4 V4.37 V (1.82%)114.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.1 V (0.88%)237.9 V3.46 V (1.44%)90.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.66 V (0.69%)238.3 V2.75 V (1.14%)72.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.32 V (0.55%)238.7 V2.18 V (0.91%)57.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.05 V (0.44%)239.0 V1.73 V (0.72%)45.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.83 V (0.35%)239.2 V1.37 V (0.57%)36.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.66 V (0.27%)239.3 V1.09 V (0.45%)28.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.56 V (0.23%)239.4 V0.92 V (0.38%)24.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.46 V (0.19%)239.5 V0.77 V (0.32%)20.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.4 V (0.17%)239.6 V0.66 V (0.27%)17.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.35 V (0.15%)239.7 V0.57 V (0.24%)15.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (0.12%)239.7 V0.46 V (0.19%)12.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.1%)239.8 V0.38 V (0.16%)10.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.08%)239.8 V0.31 V (0.13%)8.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.06%)239.9 V0.23 V (0.1%)6.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 250 feet one-way at 240V (3-Phase), you need 6 AWG copper wire. This produces a voltage drop of 5.31V (2.21%) and delivers 234.7V at the load.

What size aluminum wire is required for 25 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 5.51V (2.29%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.