🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 1.34%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 3.28V (1.58%)
Voltage at Load End205.2 VLoss: 2.79 V (1206.6 W)
Power & Breaker (125%)90.07 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A169.74 V (81.6%)38.3 V279.99 V (134.61%)73498.2 WDrop/Amp High
12 AWG3.31 mm²20 A106.66 V (51.28%)101.3 V175.94 V (84.59%)46186.2 WDrop/Amp High
10 AWG5.26 mm²30 A67.12 V (32.27%)140.9 V110.72 V (53.23%)29063.9 WDrop/Amp High
8 AWG8.37 mm²50 A42.18 V (20.28%)165.8 V69.58 V (33.45%)18264.8 WDrop/Amp High
6 AWG13.3 mm²65 A26.55 V (12.76%)181.5 V43.79 V (21.05%)11494.5 WDrop/Amp High
4 AWG21.15 mm²85 A16.69 V (8.03%)191.3 V27.54 V (13.24%)7228.2 WDrop/Amp High
3 AWG26.67 mm²100 A13.24 V (6.36%)194.8 V21.84 V (10.5%)5732.1 WDrop/Amp High
2 AWG33.62 mm²115 A10.5 V (5.05%)197.5 V17.32 V (8.33%)4547.2 WDrop/Amp High
1 AWG42.41 mm²130 A8.32 V (4.0%)199.7 V13.73 V (6.6%)3604.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.6 V (3.17%)201.4 V10.89 V (5.23%)2858.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.24 V (2.52%)202.8 V8.64 V (4.15%)2267.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.15 V (2.0%)203.8 V6.85 V (3.29%)1798.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.29 V (1.58%)204.7 V5.43 V (2.61%)1426.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.79 V (1.34%)205.2 V4.6 V (2.21%)1206.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.32 V (1.12%)205.7 V3.83 V (1.84%)1005.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.99 V (0.96%)206.0 V3.28 V (1.58%)862.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.74 V (0.84%)206.3 V2.87 V (1.38%)754.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.39 V (0.67%)206.6 V2.3 V (1.1%)603.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.16 V (0.56%)206.8 V1.92 V (0.92%)502.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.93 V (0.45%)207.1 V1.53 V (0.74%)402.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.7 V (0.33%)207.3 V1.15 V (0.55%)301.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 125 feet one-way at 208V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 2.79V (1.34%) and delivers 205.2V at the load.

What size aluminum wire is required for 250 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 3.28V (1.58%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.