275 Amp Wire Size at 100 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.97%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 2.34V (1.95%)
Voltage at Load End117.6 VLoss: 2.36 V (649.1 W)
Power & Breaker (125%)33.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 100 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A172.48 V (143.73%)0.0 V284.5 V (237.09%)47430.8 WDrop/Amp High
12 AWG3.31 mm²20 A108.38 V (90.32%)11.6 V178.78 V (148.99%)29805.5 WDrop/Amp High
10 AWG5.26 mm²30 A68.2 V (56.84%)51.8 V112.5 V (93.75%)18755.9 WDrop/Amp High
8 AWG8.37 mm²50 A42.86 V (35.72%)77.1 V70.7 V (58.92%)11786.9 WDrop/Amp High
6 AWG13.3 mm²65 A26.97 V (22.48%)93.0 V44.49 V (37.08%)7417.8 WDrop/Amp High
4 AWG21.15 mm²85 A16.96 V (14.14%)103.0 V27.98 V (23.32%)4664.6 WDrop/Amp High
3 AWG26.67 mm²100 A13.45 V (11.21%)106.5 V22.19 V (18.49%)3699.1 WDrop/Amp High
2 AWG33.62 mm²115 A10.67 V (8.89%)109.3 V17.6 V (14.67%)2934.4 WDrop/Amp High
1 AWG42.41 mm²130 A8.46 V (7.05%)111.5 V13.95 V (11.63%)2326.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.71 V (5.59%)113.3 V11.06 V (9.22%)1844.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.32 V (4.43%)114.7 V8.78 V (7.31%)1463.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.22 V (3.52%)115.8 V6.96 V (5.8%)1160.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.35 V (2.79%)116.7 V5.52 V (4.6%)920.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.83 V (2.36%)117.2 V4.67 V (3.89%)778.7 WDrop/Amp High
300 kcmil152.0 mm²285 A2.36 V (1.97%)117.6 V3.89 V (3.24%)649.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.02 V (1.69%)118.0 V3.34 V (2.78%)556.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.77 V (1.47%)118.2 V2.92 V (2.43%)486.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.42 V (1.18%)118.6 V2.34 V (1.95%)389.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.18 V (0.98%)118.8 V1.95 V (1.62%)324.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.94 V (0.79%)119.1 V1.56 V (1.3%)259.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.71 V (0.59%)119.3 V1.17 V (0.97%)194.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 100 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 100 feet one-way at 120V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 2.36V (1.97%) and delivers 117.6V at the load.

What size aluminum wire is required for 275 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 2.34V (1.95%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.