🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 3.41V (2.84%)
Voltage at Load End116.5 VLoss: 3.54 V (973.8 W)
Power & Breaker (125%)33.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A301.83 V (251.53%)0.0 V497.88 V (414.9%)83004.0 WDrop/Amp High
12 AWG3.31 mm²20 A189.67 V (158.06%)0.0 V312.87 V (260.72%)52159.6 WDrop/Amp High
10 AWG5.26 mm²30 A119.36 V (99.46%)0.6 V196.88 V (164.07%)32822.9 WDrop/Amp High
8 AWG8.37 mm²50 A75.01 V (62.51%)45.0 V123.73 V (103.11%)20627.0 WDrop/Amp High
6 AWG13.3 mm²65 A47.2 V (39.34%)72.8 V77.86 V (64.89%)12981.1 WDrop/Amp High
4 AWG21.15 mm²85 A29.68 V (24.74%)90.3 V48.96 V (40.8%)8163.0 WDrop/Amp High
3 AWG26.67 mm²100 A23.54 V (19.62%)96.5 V38.83 V (32.36%)6473.5 WDrop/Amp High
2 AWG33.62 mm²115 A18.67 V (15.56%)101.3 V30.8 V (25.67%)5135.3 WDrop/Amp High
1 AWG42.41 mm²130 A14.8 V (12.34%)105.2 V24.42 V (20.35%)4070.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.74 V (9.78%)108.3 V19.36 V (16.13%)3227.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.31 V (7.76%)110.7 V15.36 V (12.8%)2560.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.39 V (6.15%)112.6 V12.18 V (10.15%)2030.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.86 V (4.88%)114.1 V9.66 V (8.05%)1610.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.96 V (4.13%)115.0 V8.17 V (6.81%)1362.7 WDrop/Amp High
300 kcmil152.0 mm²285 A4.13 V (3.44%)115.9 V6.81 V (5.68%)1135.8 W~ ≤5%
350 kcmil177.3 mm²310 A3.54 V (2.95%)116.5 V5.84 V (4.87%)973.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.1 V (2.58%)116.9 V5.11 V (4.26%)851.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.48 V (2.06%)117.5 V4.09 V (3.41%)681.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.07 V (1.72%)117.9 V3.41 V (2.84%)567.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.65 V (1.38%)118.3 V2.73 V (2.27%)454.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.24 V (1.03%)118.8 V2.04 V (1.7%)340.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 175 feet one-way at 120V (1-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 3.54V (2.95%) and delivers 116.5V at the load.

What size aluminum wire is required for 275 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 3.41V (2.84%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.