🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.23%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 2.53V (1.22%)
Voltage at Load End205.4 VLoss: 2.55 V (1217.0 W)
Power & Breaker (125%)99.07 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A186.71 V (89.76%)21.3 V307.99 V (148.07%)88932.8 WDrop/Amp High
12 AWG3.31 mm²20 A117.33 V (56.41%)90.7 V193.54 V (93.05%)55885.3 WDrop/Amp High
10 AWG5.26 mm²30 A73.83 V (35.5%)134.2 V121.79 V (58.55%)35167.4 WDrop/Amp High
8 AWG8.37 mm²50 A46.4 V (22.31%)161.6 V76.54 V (36.8%)22100.4 WDrop/Amp High
6 AWG13.3 mm²65 A29.2 V (14.04%)178.8 V48.17 V (23.16%)13908.3 WDrop/Amp High
4 AWG21.15 mm²85 A18.36 V (8.83%)189.6 V30.29 V (14.56%)8746.1 WDrop/Amp High
3 AWG26.67 mm²100 A14.56 V (7.0%)193.4 V24.02 V (11.55%)6935.9 WDrop/Amp High
2 AWG33.62 mm²115 A11.55 V (5.55%)196.4 V19.05 V (9.16%)5502.1 WDrop/Amp High
1 AWG42.41 mm²130 A9.16 V (4.4%)198.8 V15.11 V (7.26%)4361.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.26 V (3.49%)200.7 V11.98 V (5.76%)3458.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.76 V (2.77%)202.2 V9.5 V (4.57%)2743.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.57 V (2.2%)203.4 V7.54 V (3.62%)2176.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.62 V (1.74%)204.4 V5.98 V (2.87%)1725.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.07 V (1.47%)204.9 V5.06 V (2.43%)1460.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.55 V (1.23%)205.4 V4.21 V (2.03%)1217.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.19 V (1.05%)205.8 V3.61 V (1.74%)1043.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.92 V (0.92%)206.1 V3.16 V (1.52%)912.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.53 V (0.74%)206.5 V2.53 V (1.22%)730.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.28 V (0.61%)206.7 V2.11 V (1.01%)608.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.02 V (0.49%)207.0 V1.69 V (0.81%)486.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.77 V (0.37%)207.2 V1.26 V (0.61%)365.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 125 feet one-way at 208V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 2.55V (1.23%) and delivers 205.4V at the load.

What size aluminum wire is required for 275 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 2.53V (1.22%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.