🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 150 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.47%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.03V (1.46%)
Voltage at Load End204.9 VLoss: 3.07 V (1460.4 W)
Power & Breaker (125%)99.07 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 150 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A224.05 V (107.72%)0.0 V369.58 V (177.68%)106719.4 WDrop/Amp High
12 AWG3.31 mm²20 A140.79 V (67.69%)67.2 V232.24 V (111.66%)67062.3 WDrop/Amp High
10 AWG5.26 mm²30 A88.6 V (42.6%)119.4 V146.15 V (70.26%)42200.8 WDrop/Amp High
8 AWG8.37 mm²50 A55.68 V (26.77%)152.3 V91.84 V (44.16%)26520.5 WDrop/Amp High
6 AWG13.3 mm²65 A35.04 V (16.85%)173.0 V57.8 V (27.79%)16689.9 WDrop/Amp High
4 AWG21.15 mm²85 A22.03 V (10.59%)186.0 V36.35 V (17.47%)10495.3 WDrop/Amp High
3 AWG26.67 mm²100 A17.47 V (8.4%)190.5 V28.82 V (13.86%)8323.1 WDrop/Amp High
2 AWG33.62 mm²115 A13.86 V (6.66%)194.1 V22.87 V (10.99%)6602.5 WDrop/Amp High
1 AWG42.41 mm²130 A10.99 V (5.28%)197.0 V18.13 V (8.71%)5234.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.71 V (4.19%)199.3 V14.37 V (6.91%)4149.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.91 V (3.32%)201.1 V11.4 V (5.48%)3292.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.48 V (2.64%)202.5 V9.04 V (4.35%)2611.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.35 V (2.09%)203.7 V7.17 V (3.45%)2070.7 WDrop/Amp High
250 kcmil126.7 mm²255 A3.68 V (1.77%)204.3 V6.07 V (2.92%)1752.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.07 V (1.47%)204.9 V5.06 V (2.43%)1460.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.63 V (1.26%)205.4 V4.34 V (2.08%)1252.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.3 V (1.11%)205.7 V3.79 V (1.82%)1095.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.84 V (0.88%)206.2 V3.03 V (1.46%)876.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.53 V (0.74%)206.5 V2.53 V (1.22%)730.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.23 V (0.59%)206.8 V2.02 V (0.97%)584.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.92 V (0.44%)207.1 V1.52 V (0.73%)438.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 150 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 150 feet one-way at 208V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.07V (1.47%) and delivers 204.9V at the load.

What size aluminum wire is required for 275 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.03V (1.46%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.