🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 150 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.92%
Aluminum Wire (≤3% Drop)4 AWGDrop: 3.97V (1.91%)
Voltage at Load End201.9 VLoss: 6.07 V (315.6 W)
Power & Breaker (125%)10.81 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 150 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A24.44 V (11.75%)183.6 V40.32 V (19.38%)1270.0 WDrop/Amp High
12 AWG3.31 mm²20 A15.36 V (7.38%)192.6 V25.34 V (12.18%)798.1 WDrop/Amp High
10 AWG5.26 mm²30 A9.67 V (4.65%)198.3 V15.94 V (7.67%)502.2 W~ ≤5%
8 AWG8.37 mm²50 A6.07 V (2.92%)201.9 V10.02 V (4.82%)315.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.82 V (1.84%)204.2 V6.31 V (3.03%)198.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.4 V (1.16%)205.6 V3.97 V (1.91%)124.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.91 V (0.92%)206.1 V3.14 V (1.51%)99.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.51 V (0.73%)206.5 V2.49 V (1.2%)78.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.2 V (0.58%)206.8 V1.98 V (0.95%)62.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.95 V (0.46%)207.0 V1.57 V (0.75%)49.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.75 V (0.36%)207.2 V1.24 V (0.6%)39.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.6 V (0.29%)207.4 V0.99 V (0.47%)31.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.47 V (0.23%)207.5 V0.78 V (0.38%)24.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.4 V (0.19%)207.6 V0.66 V (0.32%)20.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.33 V (0.16%)207.7 V0.55 V (0.27%)17.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.29 V (0.14%)207.7 V0.47 V (0.23%)14.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.25 V (0.12%)207.7 V0.41 V (0.2%)13.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.2 V (0.1%)207.8 V0.33 V (0.16%)10.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.17 V (0.08%)207.8 V0.28 V (0.13%)8.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (0.06%)207.9 V0.22 V (0.11%)7.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.05%)207.9 V0.17 V (0.08%)5.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 150 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 150 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 6.07V (2.92%) and delivers 201.9V at the load.

What size aluminum wire is required for 30 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 3.97V (1.91%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.