🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.07V (2.92%)
Voltage at Load End201.9 VLoss: 6.13 V (2920.7 W)
Power & Breaker (125%)99.07 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A896.21 V (430.87%)0.0 V1478.33 V (710.73%)426877.5 WDrop/Amp High
12 AWG3.31 mm²20 A563.18 V (270.76%)0.0 V928.98 V (446.62%)268249.3 WDrop/Amp High
10 AWG5.26 mm²30 A354.39 V (170.38%)0.0 V584.59 V (281.05%)168803.3 WDrop/Amp High
8 AWG8.37 mm²50 A222.71 V (107.07%)0.0 V367.37 V (176.62%)106081.9 WDrop/Amp High
6 AWG13.3 mm²65 A140.16 V (67.38%)67.8 V231.2 V (111.15%)66759.8 WDrop/Amp High
4 AWG21.15 mm²85 A88.14 V (42.37%)119.9 V145.39 V (69.9%)41981.3 WDrop/Amp High
3 AWG26.67 mm²100 A69.9 V (33.6%)138.1 V115.3 V (55.43%)33292.3 WDrop/Amp High
2 AWG33.62 mm²115 A55.45 V (26.66%)152.6 V91.46 V (43.97%)26410.0 WDrop/Amp High
1 AWG42.41 mm²130 A43.95 V (21.13%)164.0 V72.5 V (34.86%)20936.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A34.85 V (16.75%)173.2 V57.49 V (27.64%)16599.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A27.65 V (13.29%)180.4 V45.6 V (21.92%)13167.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.93 V (10.54%)186.1 V36.17 V (17.39%)10444.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.39 V (8.36%)190.6 V28.68 V (13.79%)8282.7 WDrop/Amp High
250 kcmil126.7 mm²255 A14.71 V (7.07%)193.3 V24.27 V (11.67%)7007.9 WDrop/Amp High
300 kcmil152.0 mm²285 A12.26 V (5.9%)195.7 V20.23 V (9.73%)5841.5 WDrop/Amp High
350 kcmil177.3 mm²310 A10.51 V (5.05%)197.5 V17.34 V (8.34%)5007.9 WDrop/Amp High
400 kcmil202.7 mm²335 A9.2 V (4.42%)198.8 V15.17 V (7.29%)4380.4 W~ ≤5%
500 kcmil253.4 mm²380 A7.36 V (3.54%)200.6 V12.13 V (5.83%)3504.0 W~ ≤5%
600 kcmil304.0 mm²420 A6.13 V (2.95%)201.9 V10.11 V (4.86%)2920.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.91 V (2.36%)203.1 V8.09 V (3.89%)2336.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.68 V (1.77%)204.3 V6.07 V (2.92%)1752.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 600 feet one-way at 208V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 6.13V (2.95%) and delivers 201.9V at the load.

What size aluminum wire is required for 275 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.07V (2.92%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.