🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 100 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.95%
Aluminum Wire (≤3% Drop)6 AWGDrop: 4.2V (2.02%)
Voltage at Load End204.0 VLoss: 4.05 V (210.4 W)
Power & Breaker (125%)10.81 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 100 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A16.29 V (7.83%)191.7 V26.88 V (12.92%)846.7 WDrop/Amp High
12 AWG3.31 mm²20 A10.24 V (4.92%)197.8 V16.89 V (8.12%)532.1 WDrop/Amp High
10 AWG5.26 mm²30 A6.44 V (3.1%)201.6 V10.63 V (5.11%)334.8 W~ ≤5%
8 AWG8.37 mm²50 A4.05 V (1.95%)204.0 V6.68 V (3.21%)210.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.55 V (1.23%)205.5 V4.2 V (2.02%)132.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.6 V (0.77%)206.4 V2.64 V (1.27%)83.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.27 V (0.61%)206.7 V2.1 V (1.01%)66.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.01 V (0.48%)207.0 V1.66 V (0.8%)52.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.8 V (0.38%)207.2 V1.32 V (0.63%)41.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.63 V (0.3%)207.4 V1.05 V (0.5%)32.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.5 V (0.24%)207.5 V0.83 V (0.4%)26.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.4 V (0.19%)207.6 V0.66 V (0.32%)20.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.32 V (0.15%)207.7 V0.52 V (0.25%)16.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.27 V (0.13%)207.7 V0.44 V (0.21%)13.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.22 V (0.11%)207.8 V0.37 V (0.18%)11.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.19 V (0.09%)207.8 V0.32 V (0.15%)9.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.17 V (0.08%)207.8 V0.28 V (0.13%)8.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.13 V (0.06%)207.9 V0.22 V (0.11%)7.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.11 V (0.05%)207.9 V0.18 V (0.09%)5.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.09 V (0.04%)207.9 V0.15 V (0.07%)4.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.03%)207.9 V0.11 V (0.05%)3.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 100 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 100 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.05V (1.95%) and delivers 204.0V at the load.

What size aluminum wire is required for 30 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 4.2V (2.02%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.