🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 400 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.67%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.65V (2.77%)
Voltage at Load End233.6 VLoss: 6.41 V (333.1 W)
Power & Breaker (125%)12.47 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A65.18 V (27.16%)174.8 V107.51 V (44.8%)3386.8 WDrop/Amp High
12 AWG3.31 mm²20 A40.96 V (17.07%)199.0 V67.56 V (28.15%)2128.3 WDrop/Amp High
10 AWG5.26 mm²30 A25.77 V (10.74%)214.2 V42.52 V (17.71%)1339.3 WDrop/Amp High
8 AWG8.37 mm²50 A16.2 V (6.75%)223.8 V26.72 V (11.13%)841.6 WDrop/Amp High
6 AWG13.3 mm²65 A10.19 V (4.25%)229.8 V16.81 V (7.01%)529.7 W~ ≤5%
4 AWG21.15 mm²85 A6.41 V (2.67%)233.6 V10.57 V (4.41%)333.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A5.08 V (2.12%)234.9 V8.39 V (3.49%)264.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.03 V (1.68%)236.0 V6.65 V (2.77%)209.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.2 V (1.33%)236.8 V5.27 V (2.2%)166.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.53 V (1.06%)237.5 V4.18 V (1.74%)131.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.01 V (0.84%)238.0 V3.32 V (1.38%)104.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.59 V (0.66%)238.4 V2.63 V (1.1%)82.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.26 V (0.53%)238.7 V2.09 V (0.87%)65.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.07 V (0.45%)238.9 V1.77 V (0.74%)55.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.89 V (0.37%)239.1 V1.47 V (0.61%)46.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.76 V (0.32%)239.2 V1.26 V (0.53%)39.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.67 V (0.28%)239.3 V1.1 V (0.46%)34.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.54 V (0.22%)239.5 V0.88 V (0.37%)27.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.45 V (0.19%)239.6 V0.74 V (0.31%)23.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.36 V (0.15%)239.6 V0.59 V (0.25%)18.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.27 V (0.11%)239.7 V0.44 V (0.18%)13.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 400 feet one-way at 240V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 6.41V (2.67%) and delivers 233.6V at the load.

What size aluminum wire is required for 30 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.65V (2.77%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.