40 Amp Wire Size at 400 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1 AWGDrop: 7.03V (2.93%)
Voltage at Load End233.2 VLoss: 6.78 V (469.6 W)
Power & Breaker (125%)16.63 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A86.91 V (36.21%)153.1 V143.35 V (59.73%)6021.0 WDrop/Amp High
12 AWG3.31 mm²20 A54.61 V (22.75%)185.4 V90.08 V (37.53%)3783.6 WDrop/Amp High
10 AWG5.26 mm²30 A34.37 V (14.32%)205.6 V56.69 V (23.62%)2380.9 WDrop/Amp High
8 AWG8.37 mm²50 A21.6 V (9.0%)218.4 V35.62 V (14.84%)1496.3 WDrop/Amp High
6 AWG13.3 mm²65 A13.59 V (5.66%)226.4 V22.42 V (9.34%)941.6 WDrop/Amp High
4 AWG21.15 mm²85 A8.55 V (3.56%)231.5 V14.1 V (5.87%)592.1 W~ ≤5%
3 AWG26.67 mm²100 A6.78 V (2.82%)233.2 V11.18 V (4.66%)469.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A5.38 V (2.24%)234.6 V8.87 V (3.7%)372.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.26 V (1.78%)235.7 V7.03 V (2.93%)295.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.38 V (1.41%)236.6 V5.57 V (2.32%)234.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.68 V (1.12%)237.3 V4.42 V (1.84%)185.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.13 V (0.89%)237.9 V3.51 V (1.46%)147.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.69 V (0.7%)238.3 V2.78 V (1.16%)116.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.43 V (0.59%)238.6 V2.35 V (0.98%)98.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.19 V (0.5%)238.8 V1.96 V (0.82%)82.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.02 V (0.42%)239.0 V1.68 V (0.7%)70.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.89 V (0.37%)239.1 V1.47 V (0.61%)61.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.71 V (0.3%)239.3 V1.18 V (0.49%)49.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.59 V (0.25%)239.4 V0.98 V (0.41%)41.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.48 V (0.2%)239.5 V0.78 V (0.33%)33.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.36 V (0.15%)239.6 V0.59 V (0.25%)24.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 400 feet one-way at 240V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 6.78V (2.82%) and delivers 233.2V at the load.

What size aluminum wire is required for 40 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 7.03V (2.93%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.