🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 1.59%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 8.83V (1.84%)
Voltage at Load End472.4 VLoss: 7.65 V (3973.2 W)
Power & Breaker (125%)249.42 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A651.79 V (135.79%)0.0 V1075.15 V (223.99%)338679.7 WDrop/Amp High
12 AWG3.31 mm²20 A409.58 V (85.33%)70.4 V675.62 V (140.75%)212825.9 WDrop/Amp High
10 AWG5.26 mm²30 A257.74 V (53.7%)222.3 V425.15 V (88.57%)133926.6 WDrop/Amp High
8 AWG8.37 mm²50 A161.97 V (33.74%)318.0 V267.18 V (55.66%)84164.1 WDrop/Amp High
6 AWG13.3 mm²65 A101.93 V (21.24%)378.1 V168.14 V (35.03%)52966.4 WDrop/Amp High
4 AWG21.15 mm²85 A64.1 V (13.35%)415.9 V105.74 V (22.03%)33307.5 WDrop/Amp High
3 AWG26.67 mm²100 A50.83 V (10.59%)429.2 V83.85 V (17.47%)26413.7 WDrop/Amp High
2 AWG33.62 mm²115 A40.32 V (8.4%)439.7 V66.52 V (13.86%)20953.4 WDrop/Amp High
1 AWG42.41 mm²130 A31.97 V (6.66%)448.0 V52.73 V (10.99%)16610.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.35 V (5.28%)454.7 V41.81 V (8.71%)13169.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.11 V (4.19%)459.9 V33.16 V (6.91%)10447.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.95 V (3.32%)464.1 V26.31 V (5.48%)8286.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.65 V (2.63%)467.4 V20.86 V (4.35%)6571.4 WDrop/Amp High
250 kcmil126.7 mm²255 A10.7 V (2.23%)469.3 V17.65 V (3.68%)5560.0 WDrop/Amp High
300 kcmil152.0 mm²285 A8.92 V (1.86%)471.1 V14.71 V (3.07%)4634.6 WDrop/Amp High
350 kcmil177.3 mm²310 A7.65 V (1.59%)472.4 V12.61 V (2.63%)3973.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A6.69 V (1.39%)473.3 V11.03 V (2.3%)3475.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.35 V (1.11%)474.6 V8.83 V (1.84%)2780.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.46 V (0.93%)475.5 V7.36 V (1.53%)2317.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.57 V (0.74%)476.4 V5.89 V (1.23%)1853.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.68 V (0.56%)477.3 V4.41 V (0.92%)1390.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 400 feet one-way at 480V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 7.65V (1.59%) and delivers 472.4V at the load.

What size aluminum wire is required for 300 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 8.83V (1.84%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.