🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 1.24%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.88V (1.23%)
Voltage at Load End474.1 VLoss: 5.95 V (4119.6 W)
Power & Breaker (125%)332.55 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A869.05 V (181.05%)0.0 V1433.53 V (298.65%)602097.2 WDrop/Amp High
12 AWG3.31 mm²20 A546.11 V (113.77%)0.0 V900.83 V (187.67%)378357.2 WDrop/Amp High
10 AWG5.26 mm²30 A343.66 V (71.59%)136.3 V566.87 V (118.1%)238091.7 WDrop/Amp High
8 AWG8.37 mm²50 A215.97 V (44.99%)264.0 V356.24 V (74.22%)149625.1 WDrop/Amp High
6 AWG13.3 mm²65 A135.91 V (28.31%)344.1 V224.19 V (46.71%)94162.6 WDrop/Amp High
4 AWG21.15 mm²85 A85.47 V (17.81%)394.5 V140.98 V (29.37%)59213.3 WDrop/Amp High
3 AWG26.67 mm²100 A67.78 V (14.12%)412.2 V111.8 V (23.29%)46957.7 WDrop/Amp High
2 AWG33.62 mm²115 A53.77 V (11.2%)426.2 V88.69 V (18.48%)37250.5 WDrop/Amp High
1 AWG42.41 mm²130 A42.62 V (8.88%)437.4 V70.31 V (14.65%)29529.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A33.79 V (7.04%)446.2 V55.74 V (11.61%)23413.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A26.81 V (5.58%)453.2 V44.22 V (9.21%)18572.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.26 V (4.43%)458.7 V35.08 V (7.31%)14731.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A16.86 V (3.51%)463.1 V27.81 V (5.79%)11682.5 WDrop/Amp High
250 kcmil126.7 mm²255 A14.27 V (2.97%)465.7 V23.53 V (4.9%)9884.5 WDrop/Amp High
300 kcmil152.0 mm²285 A11.89 V (2.48%)468.1 V19.62 V (4.09%)8239.2 WDrop/Amp High
350 kcmil177.3 mm²310 A10.2 V (2.12%)469.8 V16.82 V (3.5%)7063.5 WDrop/Amp High
400 kcmil202.7 mm²335 A8.92 V (1.86%)471.1 V14.71 V (3.06%)6178.4 WDrop/Amp High
500 kcmil253.4 mm²380 A7.13 V (1.49%)472.9 V11.77 V (2.45%)4942.2 WDrop/Amp High
600 kcmil304.0 mm²420 A5.95 V (1.24%)474.1 V9.81 V (2.04%)4119.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.76 V (0.99%)475.2 V7.85 V (1.63%)3295.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.57 V (0.74%)476.4 V5.88 V (1.23%)2471.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 400 feet one-way at 480V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 5.95V (1.24%) and delivers 474.1V at the load.

What size aluminum wire is required for 400 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.88V (1.23%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.