⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 450 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.51%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 6.62V (2.76%)
Voltage at Load End234.0 VLoss: 6.02 V (3127.5 W)
Power & Breaker (125%)124.71 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A733.26 V (305.53%)0.0 V1209.54 V (503.98%)381014.7 WDrop/Amp High
12 AWG3.31 mm²20 A460.78 V (191.99%)0.0 V760.07 V (316.7%)239429.1 WDrop/Amp High
10 AWG5.26 mm²30 A289.96 V (120.82%)0.0 V478.3 V (199.29%)150667.4 WDrop/Amp High
8 AWG8.37 mm²50 A182.22 V (75.93%)57.8 V300.58 V (125.24%)94684.6 WDrop/Amp High
6 AWG13.3 mm²65 A114.68 V (47.78%)125.3 V189.16 V (78.82%)59587.3 WDrop/Amp High
4 AWG21.15 mm²85 A72.11 V (30.05%)167.9 V118.95 V (49.56%)37470.9 WDrop/Amp High
3 AWG26.67 mm²100 A57.19 V (23.83%)182.8 V94.33 V (39.31%)29715.4 WDrop/Amp High
2 AWG33.62 mm²115 A45.37 V (18.9%)194.6 V74.83 V (31.18%)23572.6 WDrop/Amp High
1 AWG42.41 mm²130 A35.96 V (14.98%)204.0 V59.32 V (24.72%)18686.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A28.51 V (11.88%)211.5 V47.03 V (19.6%)14816.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A22.62 V (9.42%)217.4 V37.31 V (15.55%)11753.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.94 V (7.48%)222.1 V29.59 V (12.33%)9322.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.23 V (5.93%)225.8 V23.47 V (9.78%)7392.8 WDrop/Amp High
250 kcmil126.7 mm²255 A12.04 V (5.02%)228.0 V19.86 V (8.27%)6255.0 WDrop/Amp High
300 kcmil152.0 mm²285 A10.03 V (4.18%)230.0 V16.55 V (6.9%)5213.9 WDrop/Amp High
350 kcmil177.3 mm²310 A8.6 V (3.58%)231.4 V14.19 V (5.91%)4469.9 W~ ≤5%
400 kcmil202.7 mm²335 A7.52 V (3.14%)232.5 V12.41 V (5.17%)3909.8 W~ ≤5%
500 kcmil253.4 mm²380 A6.02 V (2.51%)234.0 V9.93 V (4.14%)3127.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.02 V (2.09%)235.0 V8.28 V (3.45%)2606.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.01 V (1.67%)236.0 V6.62 V (2.76%)2085.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.01 V (1.25%)237.0 V4.97 V (2.07%)1564.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 450 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 6.02V (2.51%) and delivers 234.0V at the load.

What size aluminum wire is required for 300 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 6.62V (2.76%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.