🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 0.6%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 1.65V (0.69%)
Voltage at Load End238.6 VLoss: 1.43 V (745.0 W)
Power & Breaker (125%)124.71 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A122.21 V (50.92%)117.8 V201.59 V (84.0%)63502.4 WDrop/Amp High
12 AWG3.31 mm²20 A76.8 V (32.0%)163.2 V126.68 V (52.78%)39904.9 WDrop/Amp High
10 AWG5.26 mm²30 A48.33 V (20.14%)191.7 V79.72 V (33.22%)25111.2 WDrop/Amp High
8 AWG8.37 mm²50 A30.37 V (12.65%)209.6 V50.1 V (20.87%)15780.8 WDrop/Amp High
6 AWG13.3 mm²65 A19.11 V (7.96%)220.9 V31.53 V (13.14%)9931.2 WDrop/Amp High
4 AWG21.15 mm²85 A12.02 V (5.01%)228.0 V19.83 V (8.26%)6245.2 WDrop/Amp High
3 AWG26.67 mm²100 A9.53 V (3.97%)230.5 V15.72 V (6.55%)4952.6 WDrop/Amp High
2 AWG33.62 mm²115 A7.56 V (3.15%)232.4 V12.47 V (5.2%)3928.8 WDrop/Amp High
1 AWG42.41 mm²130 A5.99 V (2.5%)234.0 V9.89 V (4.12%)3114.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.75 V (1.98%)235.2 V7.84 V (3.27%)2469.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.77 V (1.57%)236.2 V6.22 V (2.59%)1958.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.99 V (1.25%)237.0 V4.93 V (2.06%)1553.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.37 V (0.99%)237.6 V3.91 V (1.63%)1232.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.01 V (0.84%)238.0 V3.31 V (1.38%)1042.5 WDrop/Amp High
300 kcmil152.0 mm²285 A1.67 V (0.7%)238.3 V2.76 V (1.15%)869.0 WDrop/Amp High
350 kcmil177.3 mm²310 A1.43 V (0.6%)238.6 V2.36 V (0.99%)745.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.25 V (0.52%)238.7 V2.07 V (0.86%)651.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.0 V (0.42%)239.0 V1.65 V (0.69%)521.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.84 V (0.35%)239.2 V1.38 V (0.57%)434.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.67 V (0.28%)239.3 V1.1 V (0.46%)347.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.21%)239.5 V0.83 V (0.34%)260.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 75 feet one-way at 240V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 1.43V (0.6%) and delivers 238.6V at the load.

What size aluminum wire is required for 300 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 1.65V (0.69%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.