⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.28V (3.45%)
Voltage at Load End233.3 VLoss: 6.69 V (3475.9 W)
Power & Breaker (125%)124.71 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1222.11 V (509.21%)0.0 V2015.9 V (839.96%)635024.4 WDrop/Amp High
12 AWG3.31 mm²20 A767.97 V (319.99%)0.0 V1266.79 V (527.83%)399048.6 WDrop/Amp High
10 AWG5.26 mm²30 A483.27 V (201.36%)0.0 V797.16 V (332.15%)251112.3 WDrop/Amp High
8 AWG8.37 mm²50 A303.7 V (126.54%)0.0 V500.96 V (208.74%)157807.7 WDrop/Amp High
6 AWG13.3 mm²65 A191.13 V (79.64%)48.9 V315.27 V (131.36%)99312.1 WDrop/Amp High
4 AWG21.15 mm²85 A120.19 V (50.08%)119.8 V198.25 V (82.61%)62451.6 WDrop/Amp High
3 AWG26.67 mm²100 A95.31 V (39.71%)144.7 V157.22 V (65.51%)49525.7 WDrop/Amp High
2 AWG33.62 mm²115 A75.61 V (31.5%)164.4 V124.72 V (51.97%)39287.7 WDrop/Amp High
1 AWG42.41 mm²130 A59.94 V (24.97%)180.1 V98.87 V (41.2%)31144.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A47.52 V (19.8%)192.5 V78.39 V (32.66%)24693.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.7 V (15.71%)202.3 V62.18 V (25.91%)19588.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.9 V (12.46%)210.1 V49.32 V (20.55%)15537.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.71 V (9.88%)216.3 V39.11 V (16.3%)12321.4 WDrop/Amp High
250 kcmil126.7 mm²255 A20.06 V (8.36%)219.9 V33.09 V (13.79%)10425.0 WDrop/Amp High
300 kcmil152.0 mm²285 A16.72 V (6.97%)223.3 V27.59 V (11.49%)8689.8 WDrop/Amp High
350 kcmil177.3 mm²310 A14.34 V (5.97%)225.7 V23.65 V (9.85%)7449.8 WDrop/Amp High
400 kcmil202.7 mm²335 A12.54 V (5.23%)227.5 V20.69 V (8.62%)6516.3 WDrop/Amp High
500 kcmil253.4 mm²380 A10.03 V (4.18%)230.0 V16.55 V (6.89%)5212.5 W~ ≤5%
600 kcmil304.0 mm²420 A8.36 V (3.48%)231.6 V13.79 V (5.75%)4344.9 W~ ≤5%
750 kcmil380.0 mm²475 A6.69 V (2.79%)233.3 V11.03 V (4.6%)3475.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A5.02 V (2.09%)235.0 V8.28 V (3.45%)2606.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 750 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.69V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 300 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.28V (3.45%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.