🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.03V (4.6%)
Voltage at Load End233.3 VLoss: 6.69 V (4634.3 W)
Power & Breaker (125%)166.28 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1629.47 V (678.95%)0.0 V2687.87 V (1119.95%)1128932.3 WDrop/Amp High
12 AWG3.31 mm²20 A1023.96 V (426.65%)0.0 V1689.05 V (703.77%)709419.7 WDrop/Amp High
10 AWG5.26 mm²30 A644.35 V (268.48%)0.0 V1062.88 V (442.87%)446421.9 WDrop/Amp High
8 AWG8.37 mm²50 A404.93 V (168.72%)0.0 V667.95 V (278.31%)280547.1 WDrop/Amp High
6 AWG13.3 mm²65 A254.83 V (106.18%)0.0 V420.36 V (175.15%)176554.8 WDrop/Amp High
4 AWG21.15 mm²85 A160.25 V (66.77%)79.7 V264.34 V (110.14%)111025.0 WDrop/Amp High
3 AWG26.67 mm²100 A127.08 V (52.95%)112.9 V209.63 V (87.34%)88045.7 WDrop/Amp High
2 AWG33.62 mm²115 A100.81 V (42.01%)139.2 V166.29 V (69.29%)69844.7 WDrop/Amp High
1 AWG42.41 mm²130 A79.92 V (33.3%)160.1 V131.83 V (54.93%)55368.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A63.36 V (26.4%)176.6 V104.52 V (43.55%)43899.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A50.26 V (20.94%)189.7 V82.91 V (34.55%)34824.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A39.87 V (16.61%)200.1 V65.77 V (27.4%)27622.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.62 V (13.17%)208.4 V52.15 V (21.73%)21904.7 WDrop/Amp High
250 kcmil126.7 mm²255 A26.75 V (11.15%)213.2 V44.13 V (18.39%)18533.4 WDrop/Amp High
300 kcmil152.0 mm²285 A22.3 V (9.29%)217.7 V36.78 V (15.33%)15448.5 WDrop/Amp High
350 kcmil177.3 mm²310 A19.12 V (7.97%)220.9 V31.53 V (13.14%)13244.1 WDrop/Amp High
400 kcmil202.7 mm²335 A16.72 V (6.97%)223.3 V27.58 V (11.49%)11584.5 WDrop/Amp High
500 kcmil253.4 mm²380 A13.38 V (5.57%)226.6 V22.06 V (9.19%)9266.7 WDrop/Amp High
600 kcmil304.0 mm²420 A11.15 V (4.65%)228.9 V18.39 V (7.66%)7724.3 W~ ≤5%
750 kcmil380.0 mm²475 A8.92 V (3.72%)231.1 V14.71 V (6.13%)6179.4 W~ ≤5%
1000 kcmil506.7 mm²545 A6.69 V (2.79%)233.3 V11.03 V (4.6%)4634.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 750 feet one-way at 240V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 6.69V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 400 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.03V (4.6%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.