⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 450 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)12× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.69V (55.74%)
Voltage at Load End11.7 VLoss: 0.34 V (118.3 W)
Power & Breaker (125%)4.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 450 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A987.82 V (8231.8%)0.0 V1629.43 V (13578.62%)345735.5 WDrop/Amp High
12 AWG3.31 mm²20 A620.74 V (5172.85%)0.0 V1023.93 V (8532.79%)217259.8 WDrop/Amp High
10 AWG5.26 mm²30 A390.62 V (3255.16%)0.0 V644.34 V (5369.49%)136716.7 WDrop/Amp High
8 AWG8.37 mm²50 A245.48 V (2045.66%)0.0 V404.93 V (3374.38%)85917.5 WDrop/Amp High
6 AWG13.3 mm²65 A154.49 V (1287.38%)0.0 V254.83 V (2123.57%)54069.9 WDrop/Amp High
4 AWG21.15 mm²85 A97.15 V (809.56%)0.0 V160.25 V (1335.39%)34001.4 WDrop/Amp High
3 AWG26.67 mm²100 A77.04 V (642.0%)0.0 V127.08 V (1059.0%)26964.0 WDrop/Amp High
2 AWG33.62 mm²115 A61.11 V (509.28%)0.0 V100.81 V (840.08%)21389.9 WDrop/Amp High
1 AWG42.41 mm²130 A48.45 V (403.73%)0.0 V79.92 V (665.96%)16956.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A38.41 V (320.1%)0.0 V63.36 V (528.02%)13444.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A30.47 V (253.92%)0.0 V50.26 V (418.86%)10664.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A24.17 V (201.41%)0.0 V39.87 V (332.24%)8459.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A19.17 V (159.72%)0.0 V31.62 V (263.47%)6708.3 WDrop/Amp High
250 kcmil126.7 mm²255 A16.22 V (135.14%)0.0 V26.75 V (222.92%)5675.8 WDrop/Amp High
300 kcmil152.0 mm²285 A13.52 V (112.65%)0.0 V22.3 V (185.81%)4731.1 WDrop/Amp High
350 kcmil177.3 mm²310 A11.59 V (96.57%)0.4 V19.12 V (159.3%)4056.0 WDrop/Amp High
400 kcmil202.7 mm²335 A10.14 V (84.47%)1.9 V16.72 V (139.34%)3547.8 WDrop/Amp High
500 kcmil253.4 mm²380 A8.11 V (67.57%)3.9 V13.37 V (111.46%)2837.9 WDrop/Amp High
600 kcmil304.0 mm²420 A6.76 V (56.32%)5.2 V11.15 V (92.91%)2365.6 WDrop/Amp High
750 kcmil380.0 mm²475 A5.41 V (45.06%)6.6 V8.92 V (74.33%)1892.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.05 V (33.79%)7.9 V6.69 V (55.74%)1419.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 450 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 450 feet one-way at 12V (DC), you need 12× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 350 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.69V (55.74%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.