🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 450 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.38V (3.19%)
Voltage at Load End11.7 VLoss: 0.31 V (6.2 W)
Power & Breaker (125%)0.24 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 450 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A56.45 V (470.39%)0.0 V93.11 V (775.92%)1128.9 WDrop/Amp High
12 AWG3.31 mm²20 A35.47 V (295.59%)0.0 V58.51 V (487.59%)709.4 WDrop/Amp High
10 AWG5.26 mm²30 A22.32 V (186.01%)0.0 V36.82 V (306.83%)446.4 WDrop/Amp High
8 AWG8.37 mm²50 A14.03 V (116.89%)0.0 V23.14 V (192.82%)280.5 WDrop/Amp High
6 AWG13.3 mm²65 A8.83 V (73.56%)3.2 V14.56 V (121.35%)176.6 WDrop/Amp High
4 AWG21.15 mm²85 A5.55 V (46.26%)6.4 V9.16 V (76.31%)111.0 WDrop/Amp High
3 AWG26.67 mm²100 A4.4 V (36.69%)7.6 V7.26 V (60.51%)88.0 WDrop/Amp High
2 AWG33.62 mm²115 A3.49 V (29.1%)8.5 V5.76 V (48.0%)69.8 WDrop/Amp High
1 AWG42.41 mm²130 A2.77 V (23.07%)9.2 V4.57 V (38.06%)55.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.19 V (18.29%)9.8 V3.62 V (30.17%)43.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.74 V (14.51%)10.3 V2.87 V (23.93%)34.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.38 V (11.51%)10.6 V2.28 V (18.99%)27.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.1 V (9.13%)10.9 V1.81 V (15.06%)21.9 WDrop/Amp High
250 kcmil126.7 mm²255 A0.93 V (7.72%)11.1 V1.53 V (12.74%)18.5 WDrop/Amp High
300 kcmil152.0 mm²285 A0.77 V (6.44%)11.2 V1.27 V (10.62%)15.4 WDrop/Amp High
350 kcmil177.3 mm²310 A0.66 V (5.52%)11.3 V1.09 V (9.1%)13.2 WDrop/Amp High
400 kcmil202.7 mm²335 A0.58 V (4.83%)11.4 V0.96 V (7.96%)11.6 W~ ≤5%
500 kcmil253.4 mm²380 A0.46 V (3.86%)11.5 V0.76 V (6.37%)9.3 W~ ≤5%
600 kcmil304.0 mm²420 A0.39 V (3.22%)11.6 V0.64 V (5.31%)7.7 W~ ≤5%
750 kcmil380.0 mm²475 A0.31 V (2.57%)11.7 V0.51 V (4.25%)6.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (1.93%)11.8 V0.38 V (3.19%)4.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 450 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 450 feet one-way at 12V (DC), you need 750 kcmil copper wire. This produces a voltage drop of 0.31V (2.57%) and delivers 11.7V at the load.

What size aluminum wire is required for 20 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.38V (3.19%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.