375 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.22%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 3.22V (1.34%)
Voltage at Load End237.1 VLoss: 2.93 V (1900.4 W)
Power & Breaker (125%)155.88 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A356.45 V (148.52%)0.0 V587.97 V (244.99%)231519.3 WDrop/Amp High
12 AWG3.31 mm²20 A223.99 V (93.33%)16.0 V369.48 V (153.95%)145486.5 WDrop/Amp High
10 AWG5.26 mm²30 A140.95 V (58.73%)99.0 V232.51 V (96.88%)91551.4 WDrop/Amp High
8 AWG8.37 mm²50 A88.58 V (36.91%)151.4 V146.11 V (60.88%)57534.1 WDrop/Amp High
6 AWG13.3 mm²65 A55.75 V (23.23%)184.3 V91.95 V (38.31%)36207.5 WDrop/Amp High
4 AWG21.15 mm²85 A35.05 V (14.61%)204.9 V57.82 V (24.09%)22768.8 WDrop/Amp High
3 AWG26.67 mm²100 A27.8 V (11.58%)212.2 V45.86 V (19.11%)18056.2 WDrop/Amp High
2 AWG33.62 mm²115 A22.05 V (9.19%)217.9 V36.38 V (15.16%)14323.6 WDrop/Amp High
1 AWG42.41 mm²130 A17.48 V (7.28%)222.5 V28.84 V (12.02%)11354.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.86 V (5.78%)226.1 V22.86 V (9.53%)9002.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.0 V (4.58%)229.0 V18.14 V (7.56%)7141.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.72 V (3.63%)231.3 V14.39 V (5.99%)5664.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.92 V (2.88%)233.1 V11.41 V (4.75%)4492.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.85 V (2.44%)234.1 V9.65 V (4.02%)3800.8 WDrop/Amp High
300 kcmil152.0 mm²285 A4.88 V (2.03%)235.1 V8.05 V (3.35%)3168.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.18 V (1.74%)235.8 V6.9 V (2.87%)2716.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.66 V (1.52%)236.3 V6.03 V (2.51%)2375.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.93 V (1.22%)237.1 V4.83 V (2.01%)1900.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.44 V (1.02%)237.6 V4.02 V (1.68%)1584.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.95 V (0.81%)238.0 V3.22 V (1.34%)1267.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.46 V (0.61%)238.5 V2.41 V (1.01%)950.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 175 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.93V (1.22%) and delivers 237.1V at the load.

What size aluminum wire is required for 375 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 3.22V (1.34%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.