⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.52%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 1.38V (0.57%)
Voltage at Load End238.7 VLoss: 1.25 V (814.5 W)
Power & Breaker (125%)155.88 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A152.76 V (63.65%)87.2 V251.99 V (104.99%)99222.6 WDrop/Amp High
12 AWG3.31 mm²20 A96.0 V (40.0%)144.0 V158.35 V (65.98%)62351.3 WDrop/Amp High
10 AWG5.26 mm²30 A60.41 V (25.17%)179.6 V99.65 V (41.52%)39236.3 WDrop/Amp High
8 AWG8.37 mm²50 A37.96 V (15.82%)202.0 V62.62 V (26.09%)24657.5 WDrop/Amp High
6 AWG13.3 mm²65 A23.89 V (9.95%)216.1 V39.41 V (16.42%)15517.5 WDrop/Amp High
4 AWG21.15 mm²85 A15.02 V (6.26%)225.0 V24.78 V (10.33%)9758.1 WDrop/Amp High
3 AWG26.67 mm²100 A11.91 V (4.96%)228.1 V19.65 V (8.19%)7738.4 WDrop/Amp High
2 AWG33.62 mm²115 A9.45 V (3.94%)230.5 V15.59 V (6.5%)6138.7 WDrop/Amp High
1 AWG42.41 mm²130 A7.49 V (3.12%)232.5 V12.36 V (5.15%)4866.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.94 V (2.48%)234.1 V9.8 V (4.08%)3858.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.71 V (1.96%)235.3 V7.77 V (3.24%)3060.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.74 V (1.56%)236.3 V6.17 V (2.57%)2427.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.96 V (1.24%)237.0 V4.89 V (2.04%)1925.2 WDrop/Amp High
250 kcmil126.7 mm²255 A2.51 V (1.04%)237.5 V4.14 V (1.72%)1628.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.09 V (0.87%)237.9 V3.45 V (1.44%)1357.8 WDrop/Amp High
350 kcmil177.3 mm²310 A1.79 V (0.75%)238.2 V2.96 V (1.23%)1164.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.57 V (0.65%)238.4 V2.59 V (1.08%)1018.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.25 V (0.52%)238.7 V2.07 V (0.86%)814.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.05 V (0.44%)239.0 V1.72 V (0.72%)678.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.84 V (0.35%)239.2 V1.38 V (0.57%)543.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.63 V (0.26%)239.4 V1.03 V (0.43%)407.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 75 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 1.25V (0.52%) and delivers 238.7V at the load.

What size aluminum wire is required for 375 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 1.38V (0.57%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.