🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 40 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.04%
Aluminum Wire (≤3% Drop)8 AWGDrop: 3.56V (1.71%)
Voltage at Load End205.8 VLoss: 2.16 V (149.6 W)
Power & Breaker (125%)14.41 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 40 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A8.69 V (4.18%)199.3 V14.34 V (6.89%)602.1 WDrop/Amp High
12 AWG3.31 mm²20 A5.46 V (2.63%)202.5 V9.01 V (4.33%)378.4 WDrop/Amp High
10 AWG5.26 mm²30 A3.44 V (1.65%)204.6 V5.67 V (2.73%)238.1 WDrop/Amp High
8 AWG8.37 mm²50 A2.16 V (1.04%)205.8 V3.56 V (1.71%)149.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.36 V (0.65%)206.6 V2.24 V (1.08%)94.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.85 V (0.41%)207.1 V1.41 V (0.68%)59.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.68 V (0.33%)207.3 V1.12 V (0.54%)47.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.54 V (0.26%)207.5 V0.89 V (0.43%)37.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.43 V (0.2%)207.6 V0.7 V (0.34%)29.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.34 V (0.16%)207.7 V0.56 V (0.27%)23.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.27 V (0.13%)207.7 V0.44 V (0.21%)18.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.21 V (0.1%)207.8 V0.35 V (0.17%)14.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.17 V (0.08%)207.8 V0.28 V (0.13%)11.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.14 V (0.07%)207.9 V0.24 V (0.11%)9.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.12 V (0.06%)207.9 V0.2 V (0.09%)8.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.1 V (0.05%)207.9 V0.17 V (0.08%)7.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.09 V (0.04%)207.9 V0.15 V (0.07%)6.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.07 V (0.03%)207.9 V0.12 V (0.06%)4.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.06 V (0.03%)207.9 V0.1 V (0.05%)4.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.02%)208.0 V0.08 V (0.04%)3.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.02%)208.0 V0.06 V (0.03%)2.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 40 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 40 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.16V (1.04%) and delivers 205.8V at the load.

What size aluminum wire is required for 40 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 3.56V (1.71%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.