⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 80 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.08%
Aluminum Wire (≤3% Drop)6 AWGDrop: 4.48V (2.16%)
Voltage at Load End203.7 VLoss: 4.32 V (299.3 W)
Power & Breaker (125%)14.41 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 80 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A17.38 V (8.36%)190.6 V28.67 V (13.78%)1204.2 WDrop/Amp High
12 AWG3.31 mm²20 A10.92 V (5.25%)197.1 V18.02 V (8.66%)756.7 WDrop/Amp High
10 AWG5.26 mm²30 A6.87 V (3.3%)201.1 V11.34 V (5.45%)476.2 WDrop/Amp High
8 AWG8.37 mm²50 A4.32 V (2.08%)203.7 V7.12 V (3.43%)299.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.72 V (1.31%)205.3 V4.48 V (2.16%)188.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.71 V (0.82%)206.3 V2.82 V (1.36%)118.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.36 V (0.65%)206.6 V2.24 V (1.08%)93.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.08 V (0.52%)206.9 V1.77 V (0.85%)74.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.85 V (0.41%)207.1 V1.41 V (0.68%)59.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.68 V (0.32%)207.3 V1.11 V (0.54%)46.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.54 V (0.26%)207.5 V0.88 V (0.43%)37.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.43 V (0.2%)207.6 V0.7 V (0.34%)29.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.34 V (0.16%)207.7 V0.56 V (0.27%)23.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.29 V (0.14%)207.7 V0.47 V (0.23%)19.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.24 V (0.11%)207.8 V0.39 V (0.19%)16.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.2 V (0.1%)207.8 V0.34 V (0.16%)14.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.18 V (0.09%)207.8 V0.29 V (0.14%)12.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.14 V (0.07%)207.9 V0.24 V (0.11%)9.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.06%)207.9 V0.2 V (0.09%)8.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.05%)207.9 V0.16 V (0.08%)6.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.03%)207.9 V0.12 V (0.06%)4.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 80 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 80 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.32V (2.08%) and delivers 203.7V at the load.

What size aluminum wire is required for 40 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 4.48V (2.16%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.