⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 60 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.56%
Aluminum Wire (≤3% Drop)8 AWGDrop: 5.34V (2.57%)
Voltage at Load End204.8 VLoss: 3.24 V (224.4 W)
Power & Breaker (125%)14.41 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 60 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A13.04 V (6.27%)195.0 V21.5 V (10.34%)903.1 WDrop/Amp High
12 AWG3.31 mm²20 A8.19 V (3.94%)199.8 V13.51 V (6.5%)567.5 WDrop/Amp High
10 AWG5.26 mm²30 A5.15 V (2.48%)202.8 V8.5 V (4.09%)357.1 WDrop/Amp High
8 AWG8.37 mm²50 A3.24 V (1.56%)204.8 V5.34 V (2.57%)224.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.04 V (0.98%)206.0 V3.36 V (1.62%)141.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.28 V (0.62%)206.7 V2.11 V (1.02%)88.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.02 V (0.49%)207.0 V1.68 V (0.81%)70.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.81 V (0.39%)207.2 V1.33 V (0.64%)55.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.64 V (0.31%)207.4 V1.05 V (0.51%)44.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.51 V (0.24%)207.5 V0.84 V (0.4%)35.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.4 V (0.19%)207.6 V0.66 V (0.32%)27.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.32 V (0.15%)207.7 V0.53 V (0.25%)22.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.25 V (0.12%)207.7 V0.42 V (0.2%)17.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.21 V (0.1%)207.8 V0.35 V (0.17%)14.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.18 V (0.09%)207.8 V0.29 V (0.14%)12.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.15 V (0.07%)207.8 V0.25 V (0.12%)10.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.13 V (0.06%)207.9 V0.22 V (0.11%)9.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.11 V (0.05%)207.9 V0.18 V (0.08%)7.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.09 V (0.04%)207.9 V0.15 V (0.07%)6.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.07 V (0.03%)207.9 V0.12 V (0.06%)4.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.03%)207.9 V0.09 V (0.04%)3.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 60 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 60 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 3.24V (1.56%) and delivers 204.8V at the load.

What size aluminum wire is required for 40 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 5.34V (2.57%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.